Intermediate Care and Skilled Nursing Facility

Jurisdiction: MO Agency: Missouri DHSS Division of Regulation and Licensure
SNF (100%)
Plain-English summary

This Missouri regulation (19 CSR 30-85) establishes detailed construction, physical plant, fire safety, dietary, and administration standards for intermediate care and skilled nursing facilities licensed by the Division of Regulation and Licensure. Facility operators must comply with specific requirements for building design, structural integrity, ventilation, plumbing, fire safety, resident room dimensions, nursing unit layout, and ancillary service areas. All new construction, additions, and major remodeling projects must receive prior written division approval and conform to referenced life safety and building codes.

View official source
Regulation text
CODE OF STATE REGULATIONS 1JOHN R. ASHCROFT (11/30/21) 
Secretary of State
Rules of 
Department of Health and 
Senior Services 
Division 30—Division of Regulation and Licensure 
Chapter 85—Intermediate Care and Skilled 
Nursing Facility 
 
 Title Page 
19 CSR 30-85.012 Construction Standards for New Intermediate Care and Skilled Nursing 
 Facilities and Additions to and Major Remodeling of Intermediate Care 
 and Skilled Nursing Facilities...............................................................3 
19 CSR 30-85.022 Fire Safety and Emergency Preparedness Standards for New and Existing 
 Intermediate Care and Skilled Nursing Facilities........................................9 
19 CSR 30-85.032 Physical Plant Requirements for New and Existing Intermediate Care 
 and Skilled Nursing Facilities .............................................................14 
19 CSR 30-85.042 Administration and Resident Care Requirements for New and Existing 
 Intermediate Care and Skilled Nursing Facilities ......................................16 
19 CSR 30-85.052 Dietary Requirements for New and Existing Intermediate Care and 
 Skilled Nursing Facilities...................................................................21 
Title 19—DEP ARTMENT OF 
HEALTH AND SENIOR SERVICES 
Division 30—Division of Regulation and 
Licensure 
Chapter 85—Intermediate Care and 
Skilled Nursing Facility 
19 CSR 30-85.012 Construction Standards 
for New Intermediate Care and Skilled 
Nursing Facilities and Additions to and 
Major Remodeling of Intermediate Care 
and Skilled Nursing Facilities 
PURPOSE: This rule establishes construction 
standards for new intermediate care and 
skilled nursing facilities and additions to and 
remodeling of intermediate care and skilled 
nursing facilities. 
PUBLISHER’S NOTE: The secretary of state 
has determined that the publication of the 
entire text of the material which is incorpo-
rated by reference as a portion of this rule 
would be unduly cumbersome or expensive. 
Therefore, the material which is so incorpo-
rated is on file with the agency who filed this 
rule, and with the Office of the Secretary of 
State. Any interested person may view this 
material at either agency’s headquarters or 
the same will be made available at the Office 
of the Secretary of State at a cost not to 
exceed actual cost of copy reproduction. The 
entire text of the rule is printed here. This 
note refers only to the incorporated by refer-
ence material. 
PUBLISHER’S NOTE: All rules relating to 
long-term care facilities licensed by the Divi-
sion of Aging are followed by a Roman 
Numeral notation which refers to the class 
(either class I, II or III) of standard as desig-
nated in section 198.085.1, RSMo 1986. 
(1) Plans and specifications shall be prepared 
for the construction of all new intermediate 
care and skilled nursing facilities and addi-
tions to and remodeling of existing facilities. 
The plans and specifications shall be pre-
pared in conformance with Chapter 327, 
RSMo, by a duly registered architect or reg-
istered professional engineer. III 
(2) The facility may submit schematic and 
preliminary plans to the division showing the 
basic layout of the building and the general 
types of construction, mechanical and electri-
cal systems. The facility may submit details 
before the larger and more complicated work-
ing drawings and specifications so that neces-
sary corrections can be easily made before 
the final plans are submitted. The facility 
shall prepare and submit working drawings 
and specifications, complete in all respects, 
for approval by the division. These plans 
shall cover all phases of the construction pro-
ject, including site preparation; paving; gen-
eral construction; mechanical work, includ-
ing plumbing, heating, ventilating and air 
conditioning; electrical work; and all built-in 
equipment, including elevators, kitchen 
equipment and cabinet work. II/III 
(3) Facilities shall begin construction only 
after the plans and specifications have 
received the written approval of the division. 
Facilities shall then build in conformance 
with the approved plans and specifications. 
The facility shall notify the division within 
five (5) days after construction begins. If 
construction of the project is not started with-
in one (1) year after the date of approval of 
the plans and specifications are not complet-
ed within a period of three (3) years, the 
facility shall resubmit the plans to the divi-
sion for its approval and shall amend them, if 
necessary, to comply with the then current 
rules before construction work is started or 
continued. II/III 
(4) The facility shall be located on an all-
weather road and have easy access for vehic-
ular traffic. III 
(5) Facilities shall have access to local fire 
protection. III 
(6) The facility shall provide adequate roads 
and walks within the lot lines to the main 
entrance and service entrance. III 
(7) In any new addition, an existing licensed 
facility shall provide all required ancillary 
service areas, proportional to the number of 
new beds. Ho wever, for e xisting facilities, 
these support service areas may be reduced 
by the amount of existing areas that meet new 
facility requirements. New support areas 
required in this project, whether they are to 
serve the new beds or the existing beds, shall 
comply with the rules for new facilities. III 
(8) Facilities shall have administrative and 
public areas as listed: business office, admin-
istrator’s office (business office and adminis-
trator’s office may be combined); director of 
nurses’ office; lobby and waiting room (may 
be combined); public restrooms for each sex; 
and public telephone. III 
(9) The facility shall provide recreation, 
occupational therapy, activity and residents’ 
dining space at a ratio of at least thirty (30) 
square feet for each resident. II 
(10) Facilities shall provide a bulk sto rage 
area consisting of a locked room, shelving, 
bins and large cans for storing long-term sup-
plies of food and other dietary materials 
above the floor in a dry room with adequate 
ventilation, cool, but not freezing. The bulk 
storage area shall be one (1) square foot per 
bed, but in no case shall it be less than one 
hundred (100) square feet. III 
(11) Facilities shall have dry short-term stor-
age areas for daily food supplies and other 
dietary materials. The dry short-term storage 
area may include the space required for bulk 
storage. III 
(12) A facility shall provide a preparation 
area for wrapping removal, vegetable clean-
ing and peeling and meat cutting. III 
(13) Facilities shall provide adequate cooking 
and baking areas. III 
(14) A facility shall have a salad and sand-
wich preparation area for the preparation of 
cold foods. III 
(15) Facilities shall provide a tray preparation 
and loading area for preparing trays for resi-
dents’ food delivery and food cart loading. III 
(16) A facility shall provide a pot and pan 
washing area consisting of a three (3)-com-
partment sink with a double drainboard for 
the washing of utensils during the food prepa-
ration period. III 
(17) Facilities shall have a dishwashing area 
provided with a soiled dish receiving counter, 
space for scraping with a garbage grinder, 
prerinse sink, counter for racking dishes, 
dishwasher, clean dish counter, dish rack 
storage and an exhaust fan. II/III 
(18) A facility shall have a dish sto rage area 
with shelves adjacent to the tray preparation 
area. III 
(19) Facilities shall provide refrigerators of 
adequate capacity in all kitchens and other 
preparation centers where perishable foods 
will be stored. A minimum of two (2) sepa-
rate sections or boxes shall be provided in the 
main kitchen; one (1) for meat and dairy 
products and one (1) for general storage. III 
(20) The refrigerators’ compressors and evap-
orators shall have sufficient capacity to main-
tain temperatures of thirty-five degrees 
Fahrenheit (35°F) in the meat and dairy 
boxes and forty degrees Fahrenheit (40°F) in 
 CODE OF STATE REGULATIONS 3ROBIN CARNAHAN (9/30/08) 
Secretary of State
Chapter 85—Intermediate Care and Skilled Nursing Facility 19 CSR 30-85
the general storage boxes when the boxes are 
being used for those purposes. II 
(21) These compressors shall be automatical-
ly controlled. III 
(22) Compressors, piping and evaporators 
shall be tested for leaks and capacity. Certifi-
cation of these tests shall be made available to 
the division. III 
(23) A facility shall have an office area for 
planning menus and food purchases next to 
the dietary area. III 
(24) Kitchen shall have handwashing sinks. 
III 
(25) A facility shall have a janitor’s area, 
exposed or in a closet, in or near the kitchen, 
that contains a floor receptor or service sink. 
III 
(26) A garbage removal area with garbage 
and trash cans located inconspicuously shall 
be easily accessible from both the kitchen and 
the service drive. III 
(27) Housekeeping areas shall be provided as 
listed: clean linen area, soiled linen area and 
laundry area. II 
(28) The facility shall have a designated phys-
ical therapy area large enough to give rehabil-
itative care to physically disabled residents. 
This area shall be sized to accommodate all 
equipment and activities in the facility’s pro-
posed physical therapy program. In no case 
shall this area be less than two hundred (200) 
square feet. III 
(29) The facility shall provide the following 
elements: treatment areas and equipment as 
dictated by the facility’s physical therapy pro-
gram; a handwashing sink; an exercise area; 
storage for clean linen, supplies and equip-
ment; a toilet room located in the physical 
therapy room or within the immediate area of 
the physical therapy department; and an 
office or sufficient space for the physical 
therapy director’s desk and file. The physical 
therapy area may be located adjacent to an 
occupational therapy area and share any or all 
of the required elements providing that the 
sharing of elements conforms with the facili-
ty’s therapy programs. III 
(30) If there is a designated occupational 
therapy area, it shall be large enough to 
accommodate all the equipment and activities 
in the facility’s proposed occupational thera-
py program. When the facility locates physi-
cal therapy and occupational therapy in the 
same area, there shall be a space that can be 
separated from the rest of the area if ceram-
ics, sculpture, minor woodwork and light 
mechanical work are a part of the occupation-
al therapy program. III 
(31) Facilities shall provide a maintenance 
room or area. II 
(32) A facility shall provide an employees’ 
dressing or locker room with separate 
restrooms for each sex. III 
(33) Facilities shall provide storage rooms as 
listed: general sto rage—ten (10) square feet 
per bed for the first fifty (50) beds, plus eight 
(8) square feet per bed for the next twenty-
five (25) beds, plus five (5) square feet per 
bed for any additional beds over seventy-five 
(75). No storage room shall be less than one 
hundred (100) square feet of floor space. The 
required residents’ clothes sto rage room and 
storage for outdoor equipment may be includ-
ed in the minimum area required for general 
storage. III 
(34) A continuous system of unobstructed 
corridors, referred to as required corridors, 
shall extend through the enclosed portion of 
each story of the building. These corridors 
will connect all rooms and spaces with each 
other and with all entrances, exit ways and 
elevators, with the following exceptions: 
work suites, such as the administrative suite 
and dietary area, occupied primarily by 
employed personnel may contain corridors or 
aisles as necessary, and will not be subject to 
the rules applicable to required corridors. 
Areas may be open to this system as permit-
ted by the 1985 edition of the Life Safety 
Code, for those facilities with plans approved 
on or before December 31, 1998. All facili-
ties with plans submitted for approval on or 
after January 1, 1999, shall comply with the 
provisions of the 1997 Life Safety Code, 
incorporated by reference in this rule. II/III 
(35) A facility shall provide a personal care 
room with barber and beauty shop facilities. 
III 
(36) There shall be an oxygen sto rage room 
that is surrounded by one (1)-hour rated con-
struction with a powered or gravity vent to 
the outside. II 
(37) Facilities shall have one (1) or more 
nursing units. A nursing unit shall not exceed 
a maximum of sixty (60) resident beds. Each 
nursing unit shall be a single floor continuous 
area which does not require resident care 
traffic to traverse other areas. A facility shall 
not locate a resident room door more than 
one hundred forty feet (140') from the nurs-
es’ station and the dirty utility room. II 
(38) Resident room area shall be a minimum 
of eighty (80) square feet per bed in multiple 
bed resident rooms, and one hundred (100) 
square feet per bed in one (1)-bed resident 
rooms. A continuous aisle not less than three 
feet (3') wide shall be available around the 
foot and along both sides of each bed. Facil-
ities shall locate beds to avoid drafts, exces-
sive heat and other residents discomforts. 
Typical minimum clear dimensions for the 
bed area in resident rooms shall be as fol-
lows: 
 1-Bed 10' 6" × 9' 3" 
 2-Bed 10' 6" × 15' 6" 
 3-Bed 10' 6" × 21' 9" 
 4-Bed 18' 0" × 15' 6" 
Heating units and handwashing sinks may 
protrude into this required space. II 
(39) To provide for the isolation of a resi-
dent(s) with a communicable disease(s), each 
unit shall have at least two (2) private resident 
rooms provided with a separate room 
equipped with a toilet and handwashing sink 
to serve the isolation room only. III 
(40) Each resident shall have a wardrobe, 
locker or closet. A clothes rod and shelf shall 
be provided. III 
(41) No room shall be occupied by more than 
four (4) beds. III 
(42) No resident shall be housed in a room in 
which the outside grade line is more than 
three feet (3') above the floor level on the 
window side of the resident room for a dis-
tance of at least fifteen feet (15') from the 
outside wall of the resident room. The resi-
dent rooms shall be outside rooms with min-
imum window sizes as follows: 
1-Bed 10 square feet 
2-Bed 16 square feet 
3-Bed 24 square feet 
4-Bed 32 square feet 
These areas are for total window size includ-
ing frames. III 
(43) Each resident, without entering the gen-
eral corridor area, shall have access to a toilet 
room. III 
(44) One (1) toilet room shall serve no more 
than six (6) beds and no more than two (2) 
resident rooms. II/III 
(45) The toilet room shall contain a water 
closet and a lavatory. II 
4 CODE OF STATE REGULATIONS (9/30/08) ROBIN CARNAHAN 
Secretary of State
19 CSR 30-85—DEPARTMENT OF HEALTH AND 
 SENIOR SERVICES Division 30—Division of Regulation and Licensure

(46) If each resident room contains a hand-
washing sink, the may omit the handwashing 
sink from a toilet room that serves adjacent 
resident rooms. When a handwashing sink is 
located within the same room as the toilet, 
the minimum area of a room shall be thirty 
(30) square feet. If the room contains only a 
toilet, the minimum area of the room shall be 
eighteen (18) square feet. III 
(47) Each nursing unit shall have a centrally 
located nurses’ work station with a work 
counter and sto rage space for charts. The 
entire counter shall have a four foot (4') dis-
tance between the wall located behind the 
counter and the edge of the counter nearest 
the wall. III 
(48) Facilities shall provide a medicine prepa-
ration room next to each nurses’ station that 
has at least sixty (60) square feet of useable 
floor space. Facilities shall provide a special 
locked medication cabinet for sto rage of the 
Class II medications inside the locked medi-
cation cabinet. If the outer cabinets are not 
locked, the facility must provide a closer and 
hardware that cannot be left unlocked on the 
door to the medicine room. A facility is also 
required to have the following in the medicine 
room: a work counter, handwashing sink, 
under cabinet sto rage, a medicine refrigera-
tor, adequate lighting and provisions for 
proper temperature control. II/III 
(49) Each nursing unit shall have a clean util-
ity room accessible directly from the nursing 
unit corridor and near enough to the nurses’ 
station to facilitate control by the nurses. The 
floor and walls shall have impervious sur-
faces. The facility shall provide this room 
with adequate lighting and heating, a hand-
washing sink and at least one (1) locking cab-
inet. II/III 
(50) Each nursing unit shall have a dirty util-
ity room which is accessible directly from 
the nursing unit corridor. The floor shall have 
an impervious surface and the walls shall 
have impervious surfaces to a minimum 
height of five feet (5') above the floor. The 
room shall be provided with adequate lighting 
and heating, a double sink, clinic sink and at 
least one (1) locking cabinet. III 
(51) Each nursing unit shall contain one (1) 
training or handicapped toilet per sex, each 
with a floor area of at least five feet by six 
feet (5' × 6'). This toilet may be located in 
the central bath. III 
(52) Each nursing unit shall have a separate 
bathroom for each sex. II 
(53) Tubs shall be institutional-type, free 
standing with a minimum of three feet (3') 
clearance from the wall on each side and four 
feet (4') at the end. The shower shall be a 
minimum of four feet (4') wide and of ample 
length for a wheelchair resident. Thirty-inch 
by sixty-inch (30" × 60") Americans with 
Disability Act (ADA)-approved showers will 
be accepted. The facility may replace 
required institutional-type tub(s) with 
whirlpool tubs or other types of bathing fix-
tures. III 
(54) The aggregate number of tubs or show-
ers or both shall not be less than one for each 
fifteen (1:15) beds on each floor. II/III 
(55) The facility shall provide a locked cabi-
net in or near each bathroom for the sto rage 
of cleaning supplies. III 
(56) Centralized bathing facilities shall have 
fixed partitions or fire-resistant curtains to 
provide a private compartment for each water 
closet, bathtub and shower. Curtains or doors 
shall be installed on access openings. III 
(57) Clean linen storage with adequate shelv-
ing is required in each nursing unit. III 
(58) Each nursing unit must have a stretcher 
and wheelchair parking area. III 
(59) Equipment and supply sto rage is 
required in each nursing unit. III 
(60) Required corridors shall be at least eight 
feet (8') wide and shall be wider at elevators 
and other points of traffic concentration. No 
part of the area of any required corridor or 
aisle shall be counted as part of the required 
area of any space adjacent to the corridor or 
aisle. II/III 
(61) The width of stairways shall not be less 
than three feet eight inches (3' 8"). The width 
shall be measured between handrails where 
handrails project more than three and one-
half inches (3 1/2"). II/III 
(62) Doors from sleeping and treatment areas 
through which residents will pass shall be at 
least forty-four inches (44") wide. Doors to 
centralized toilets, bathrooms, hair care 
salons and small day rooms shall be at least 
thirty-six inches (36") wide. Doors to indi-
vidual toilets adjacent to resident rooms shall 
be at least thirty-two inches (32") wide. II 
(63) Exit doors shall swing outward. Doors to 
rooms shall swing into the rooms they serve. 
Doors to small toilet rooms may swing out-
ward into the next room and, if they swing 
inward, they shall be equipped for emergency 
access. No doors shall swing into required 
corridors or aisles except doors to janitors’ 
closets, linen closets or doors to similar small 
spaces that are open only temporarily. II 
(64) Ceilings shall be at least eight feet (8'). 
Ceilings in corridors, sto rage rooms, toilet 
rooms and other minor rooms shall not be 
less than seven feet six inches (7' 6"). Sus-
pended tracks, rails and pipes located in the 
normal traffic path shall be at least six feet 
eight inches (6' 8") above the floor. III 
(65) Drinking fountains shall be located in or 
near the lobby and recreation area and in each 
nursing unit. The fountain shall be accessible 
to residents in wheelchairs. III 
(66) Facilities with plans approved on or 
before December 31, 1998, shall comply 
with the American National Standards Inst-
itute (ANSI) publication A117.1, 1971, Mak-
ing Buildings and Facilities Accessible to, and 
Useable by, the Physically Handicapped. All 
new facilities whose plans were submitted to 
the division on or after January 1, 1999, shall 
comply with ANSI A117.1, 1992, Making 
Buildings and Facilities Accessible to, and 
Useable by, the Physically Handicapped, 
incorporated by reference in this rule. III 
(67) Handrails shall be provided on both 
sides of all corridors and aisles used by resi-
dents. Corridor handrails shall have ends 
return to the wall. III 
(68) All stairways shall have handrails on 
both sides. II 
(69) Facilities shall provide grab bars or 
handrails, secured in proper positions to 
facilitate the bodily movements of residents, 
next to all bathtubs, within all showers and on 
at least one (1) side of all toilets. II 
(70) Lavatories shall be positioned to be 
accessible to wheelchair residents and shall 
not have cabinets underneath or any other 
unnecessary obstruction to the maneuverabil-
ity of wheelchairs. III 
(71) The facility shall provide mirrors in each 
resident’s room or adjoining toilet room. 
Mirrors shall be at least three feet (3') high 
with the bottom edge located no more than 
three feet four inches (3' 4") above the floor 
or the facility may use framed tilting 
mirror(s). III 
 CODE OF STATE REGULATIONS 5ROBIN CARNAHAN (9/30/08) 
Secretary of State
Chapter 85—Intermediate Care and Skilled Nursing Facility 19 CSR 30-85
(72) Facilities shall provide fire-resistant 
divider curtains attached to the ceiling or 
walls in all resident rooms other than private 
or single bedrooms. A facility shall place 
these divider curtains to provide complete 
privacy for each bed. III 
(73) All new facilities and additions to all 
areas of existing facilities which undergo 
major remodeling, shall be of sufficient 
strength in all their parts to resist all stresses 
imposed by dead loads, live loads and lateral 
or uplift forces such as wind, without exceed-
ing, in any of the structural materials, the 
allowable working stresses established for 
these materials by generally accepted good 
engineering practice. II 
(74) The following unit live loads shall be the 
minimum distributed live loads acceptable for 
the occupancies listed: 
(A) Facility bedrooms and all adjoining 
service rooms which compose a typical nurs-
ing unit (except solariums and corridors)—
forty pounds per square foot (40 psf); II 
(B) Solariums, corridors in nursing units 
and all corridors above the first floor, exami-
nation and treatment rooms, laboratories, toi-
let rooms and locker rooms—sixty (60) psf; 
II 
(C) Offices, conference room, library, 
kitchen, corridors and other public areas on 
first the floor—eighty (80) psf; II 
(D) Stairways, laundry, large rooms used 
for dining, recreation or assembly areas and 
workshops—one hundred (100) psf; II 
(E) Records file room, sto rage and sup-
ply—one hundred twenty-five (125) psf; II 
(F) Mechanical equipment room—one 
hundred fifty (150) psf; II 
(G) Roofs (except use increased value 
where snow and ice may occur)—twenty (20) 
psf; and II 
(H) Wind—as required by local conditions 
but not less than fifteen (15) psf. II 
(75) For live loads of one hundred (100) 
pounds or less per square foot, the design live 
load on any member supporting one hundred 
fifty (150) square feet or more may be 
reduced at the rate of eight hundredths of a 
percent (0.08%) per square foot of area sup-
ported by the member, except that no reduc-
tions shall be made for roof live loads or for 
live loads of areas to be occupied as places of 
public assembly. The reduction shall exceed 
neither “R”, as determined by the following 
formula nor sixty percent (60%): II 
 D + L R = 100 × _______________ 
 4.33 L 
where 
R = reduction in percent; 
D = dead load per square foot of area sup-
ported by the member; and 
L = design live load per square foot of area 
supported by the member. 
(76) For live loads exceeding one hundred 
(100) psf, no reduction shall be made, except 
that the design live loads on columns may be 
reduced twenty percent (20%). II 
(77) Floor areas where partition positions are 
subject to change shall be designed to support 
a uniformly distributed load of twenty-five 
(25) psf in addition to all other loads. II 
(78) Foundations shall rest on natural solid 
ground or properly compacted fill and shall 
be carried to a depth of not less than one foot 
(1') below the estimated frost line or shall 
rest on leveled rock or load-bearing piles 
when solid ground is not encountered. Foot-
ings, piers and foundation walls shall be ade-
quately protected against deterioration from 
the action of groundwater. A facility shall 
take reasonable care to establish proper soil 
bearing values for the building site soil. If the 
bearing capacity of a soil is in question, a 
recognized load test may be used to deter-
mine the safe bearing value. II 
(79) All facilities with plans approved 
between June 10, 1981 and December 31, 
1998, shall comply with the 1985 edition of 
the Life Safety Code , and all new facilities 
with plans approved on or after January 1, 
1999, shall comply with the 1997 edition of 
the Life Safety Code (National Fire Protection 
Association NFP A 101), which are incorpo-
rated by reference in this rule. No provision 
of the 1997 code will be enforced if it is more 
restrictive than the code of original plan 
approval. Facilities may only use the fire 
safety evaluation system found in the 1995 
NFP A 101A, incorporated by reference in 
this rule, if necessary to justify variance from 
the text of the Life Safety Code and not as a 
guide for the total design of a new facility. II 
(80) Facilities with plans approved on or 
before December 31, 1998, shall comply 
with the fire-resistant rating of structural ele-
ments equal to those required by the 1985 
Life Safety Code (NFP A 101). Facilities with 
plans approved on or after January 1, 1999, 
shall comply with the fire-resistant rating of 
structural elements equal to those required by 
the 1997 Life Safety Code (NFP A 101), 
incorporated by reference in this rule. All 
facilities shall meet the following additional 
requirement: exterior walls less than thirty 
feet (30') from an adjacent building, property 
line or parallel wing shall have a two (2)-hour 
fire-resistant rating. This distance may be 
reduced to fifteen feet (15') if a one (1)-hour 
rated wall is provided with sprinkler protec-
tion for each window. II 
(81) Doors between rooms and the required 
corridors shall not have louvres or transoms. 
They shall be one and three-fourths inches 
(1 3/4") solid-core wood doors or metal 
doors with equivalent or greater fire-resis-
tance. II 
(82) Laundry and trash chutes, where used, 
shall be of fire-resistant material and installed 
with a flushing ring, vent to atmosphere and 
floor drain in the basement. Facilities shall 
provide an automatic sprinkler at the top of 
each laundry and trash chute. Each floor shall 
have a self-closing one and one-half (1 1/2)-
hour B-label fire door that shall not open to a 
corridor. II 
(83) Hardware on toilet room doors shall be 
operable from both the inside and the outside. 
II 
(84) The floors of toilets, baths, bedpan 
rooms, pantries, utility rooms and janitors’ 
closets shall have smooth, waterproof sur-
faces which are wear-resistant. The floors of 
residents’ rooms shall be smooth and easily 
cleaned. The floors of kitchens and food 
preparation areas shall be waterproof, grease-
proof, smooth and resistant to heavy wear. 
II/III 
(85) The walls of all rooms where food and 
drink are prepared, served or stored shall 
have a smooth surface with painted or equally 
washable finish. At the base, they shall be 
waterproof and free from spaces which may 
harbor ants and roaches. The walls of 
kitchens, sculleries, utility rooms, baths, 
showers, dishwashing rooms, janitors’ closets 
and spaces with sinks shall have waterproof 
painted, glazed or similar finishes to a point 
above the splash and spray line. III 
(86) The ceilings of all sculleries, kitchens 
and other rooms where food and drink are 
prepared shall be painted with washable 
paint. III 
(87) All floor construction shall be complete-
ly of noncombustible material regardless of 
the construction type of the building. II 
(88) All new floor covering installed and used 
in new and existing licensed facilities on or 
6 CODE OF STATE REGULATIONS (9/30/08) ROBIN CARNAHAN 
Secretary of State
19 CSR 30-85—DEPARTMENT OF HEALTH AND 
 SENIOR SERVICES Division 30—Division of Regulation and Licensure

 CODE OF STATE REGULATIONS 7ROBIN CARNAHAN (9/30/08) 
Secretary of State
Chapter 85—Intermediate Care and Skilled Nursing Facility 19 CSR 30-85
after January 1, 1999, shall be Class I in non-
sprinklered buildings and Class II in sprin-
klered buildings. Class I has a critical radiant 
flux of zero point forty-five (0.45) or more 
watts per square centimeter when tested 
according to the 1995 NFP A 253, incorporat-
ed by reference in this rule. Class II has a 
critical radiant flux of zero point twenty-two 
(0.22) or more watts per square centimeter 
when tested according to the 1995 NFP A 
253. Those facilities who installed new floor 
covering on or before December 31, 1998, 
shall comply with the requirements of the 
1978 edition of the NFP A 253. III 
(89) A facility shall furnish and install the 
heating system, steam system, boilers and 
ventilation to meet all requirements of local 
and state codes and NFP A regulations. II/III 
(90) The building shall be heated by a two 
(2)-pipe steam system, a forced hot water sys-
tem, a forced hot air system, a system of elec-
trical heating elements or a combination of 
two (2) or more of these systems. No open 
flame space heaters or space heaters receiv-
ing combustion air from the heated space 
shall be used. Facilities shall not depend 
upon fireplaces for required heating. III 
(91) The heating system shall be capable of 
heating resident-occupied areas to a tempera-
ture of eighty degrees Fahrenheit (80°F) 
(27°C) at the winter design temperature. In 
spaces where radiant panel heating is used, 
facilities may reduce the temperature as 
required to maintain an equivalent comfort 
level. III 
(92) The heating system shall have automatic 
controls adequate to provide comfortable 
conditions in all portions of the building at all 
times. III 
(93) Neither the heating nor the ventilating 
system shall require the circulation of air 
through openings in the required corridor 
partitions except for the delivery of ventilat-
ing air from corridors through each room 
door at a velocity of not more than two hun-
dred fifty feet (250') per minute when the 
door is closed and the space under it is not 
over one inch (1") in height. No louvres shall 
be installed in doors in required corridor par-
titions. II/III 
(94) A facility with plans approved on or 
after January 1, 1999, shall install an air-con-
ditioning system, or individual room air-con-
ditioning units, that meet all the 1996 NFP A 
90A requirements, incorporated by reference 
in this rule. The systems or units must be 
capable of maintaining resident-use areas at 
eighty-five degrees Fahrenheit (85°F) 
(29.4°C) at the summer design temperature. 
Those facilities with plans approved on or 
before December 31, 1998, shall comply 
with the NFP A 90A requirements as refer-
enced in the 1985 Life Safety Code. II/III 
(95) V entilation requirements given in Table 
I—V entilation Requirements shall be met. 
II/III
TABLE I VENTILATION REQUIREMENTS 
 Minimum Air 
 Pressure Changes of Outdoor Minimum Total Air All Air Exhausted 
 Relationship to Air Per Hour Changes Per Hour Directly to Air Returned From 
Area Designation Adjacent Areas Supplied to Room Supplied to Room Outdoors This Room 
 
Patient Area Corridor P Optional 2 Optional Optional 
 
Physical Therapy N 2 4 Optional Optional 
Occupational Therapy N 2 4 Optional Optional 
Soiled Work Room 
 or Soiled Holding N 2 10 Y es No 
*Toilet Room N Optional 6 Y es No 
Bathroom N Optional 6 Y es No 
Janitors’ Closet(s) N Optional 6 Y es No 
Linen and Trash 
 Chute Room N Optional 6 Y es No 
Food Preparation 
 Center E 2 6 Y es Optional 
Warewashing Room N Optional 6 Yes No 
Dietary Day Storage V Optional 2 Y es No 
Laundry, General V 2 6 Y es No 
Soiled Linen Sorting 
 and Storage N Optional 10 Y es No 
P = Positive 
N = Negative 
E = Equal 
V = V ariable 
*Up to 75 cubic feet per minute (cfm) of make-up air for each patient room toilet may be supplied to the corridor and need not be supplied 
directly to the room. 
NOTE: In the interest of energy conservation, energy saving design innovations that are not in strict conformance with these re quirements, 
 which do not adversely affect direct patient care, will be acceptable if approved in writing by the Division of Agin g. 
(96) The entire plumbing system and its 
maintenance and operation shall comply with 
the requirements of all applicable local and 
state codes including the requirements set 
forth in this rule and with the requirements of 
the 1987 National Plumbing Code, which is 
incorporated by reference in this rule. II/III 
(97) Plumbing fixtures that require hot water 
and are resident-accessible shall be supplied 
with water thermostatically controlled to pro-
vide a water temperature of between one hun-
dred twenty degrees Fahrenheit (120°F) 
(49°C) and one hundred five degrees Fahren-
heit (105°F) (41°C) at the fixture or faucet. 
I/II 
(98) The hot water heating equipment shall 
have sufficient capacity to supply five (5) gal-
lons (19 l) of water at one hundred twenty 
degrees Fahrenheit (120°F) (49°C) per hour 
per bed for nursing home fixtures or faucets, 
and eight (8) gallons (30 l) of water at one 
hundred sixty degrees Fahrenheit (160°F) 
(71.1°C) per hour per bed for kitchen and 
laundry. The division may accept lesser 
capacities following submission of the calcu-
lation for the anticipated demand of all fix-
tures and equipment in the building. II 
(99) Pipes shall be sized to supply water to all 
fixtures with a minimum pressure of fifteen 
pounds per square inch (15 psi) (1.02 atmo-
spheres) at the top floor fixture during maxi-
mum demand periods. All plumbing fixtures 
except water closets, urinals and drinking 
fountains shall have both hot and cold water 
supplies. III 
(100) Facilities shall protect every supply 
outlet or connection to a fixture or appliance 
against back flow as provided by the 1987 
National Plumbing Code , incorporated by 
reference in this rule. All faucets to which 
hoses can be attached, all spray fittings and 
all other fittings that could deliver water to 
points below overflow lines, shall be 
equipped with vacuum breakers. II/III 
(101) Wherever the usage of fixtures or appli-
ances will permit, water supplied to all fix-
tures, open tanks and equipment shall be 
introduced through a suitable air gap between 
the water supply and the flood level of the 
fixture. II 
(102) Hot water circulating mains and risers 
shall be run from the hot sto rage tank to a 
point directly below the highest fixture at the 
end of each branch main. III 
(103) Where the building is higher than three 
(3) stories, each riser shall be circulated. III 
(104) Water pipe sizes shall be equal to or 
greater than those prescribed by the 1987 
National Plumbing Code , incorporated by 
reference in this rule. III 
(105) All fixtures and equipment shall be 
connected through traps to soil and waste pip-
ing and to the sewer and they shall all be 
properly trapped and vented to the outside. II 
(106) Courts, yards and drives which do not 
have natural drainage from the building shall 
have catch basins and drains to low ground, 
storm-water system or dry wells. III 
(107) Facilities where gas-fired equipment is 
to be installed for use on or after January 1, 
1999, shall provide and install all gas piping, 
fittings, tanks and specialties in compliance 
with the 1996 NFP A 54, Installation of Gas 
Appliances and Gas Piping , the 1995 NFP A 
58, Storage and Handling of Liquefied 
Petroleum Gases, incorporated by reference 
in this rule, and the instructions of the gas 
supplier, except where more strict require-
ments are stated. Facilities which installed 
gas-fired equipment on or before December 
31, 1998, shall ensure that the installation 
was in compliance with the instructions and 
requirements outlined in the NFP A 54 and 
NFP A 58 as referenced in the 1985 Life Safe-
ty Code. Where liquefied petroleum gas 
(LPG) is used, the Missouri Department of 
Agriculture also requires compliance with its 
rules. II 
(108) Where gas piping enters the building 
below grade, it shall have an outside vent as 
follows: A concrete box, eighteen inches by 
eighteen inches (18" × 18") with three-inch 
(3") thick walls, of a height to rest on top of 
the entering gas pipe, and top of the box to 
come within six inches (6") of top grade. The 
box shall be filled with coarse gravel. A one-
inch (1") upright vent line shall be to one-half 
(1/2) the depth of the box and extend twelve 
inches (12") above top grade with a screened 
U-vent looking down. The vent line is to be 
anchored securely to the building wall. II 
(109) Facilities shall not install gas-fired 
equipment in any resident bedroom except 
that through-wall gas heating units may be 
used if vented directly to the outside, take 
combustion air directly from the outside and 
provide a complete separation of the combus-
tion system from the atmosphere of the occu-
pied area. II 
(110) In facilities where oxygen systems are 
installed on or after January 1, 1999, the 
facilities shall install the oxygen piping, out-
lets, manifolds, manifold rooms and sto rage 
rooms in accordance with the requirements of 
the 1993 NFP A 99, incorporated by reference 
in this rule. In facilities where oxygen sys-
tems were installed on or before December 
31, 1998, facilities shall ensure that the 
installation was in compliance with NFP A 99 
as required and referenced in the 1985 Life 
Safety Code. I/II 
(111) The building sanitary drain system may 
be cast iron, steel, copper or plastic if 
installed in compliance with the National 
Plumbing Code, current edition. III 
(112) Each main, branch main, riser and 
branch to a group of fixtures of the water sys-
tem shall be valved. III 
(113) To prevent condensation, facilities shall 
cover cold water mains in occupied spaces 
with approved vapor-proof insulation. III 
(114) To prevent freezing, facilities shall 
insulate all pipes in outside walls. III 
(115) Facilities shall test soil, waste, vent and 
drain lines according to the requirements of 
the 1987 National Plumbing Code, incorpo-
rated by reference in this rule. The facility 
shall make certification of these tests avail-
able to the division. III 
(116) After installation and before the nurs-
ing home is operating, the facility shall disin-
fect the entire water distribution system, both 
hot and cold, and all connecting equipment 
by one (1) of the methods described in the 
1987 National Plumbing Code, incorporated 
by reference in this rule. III 
(117) Water softeners, if used, shall be con-
nected to the hot water supply only or con-
nected so that water used for cooking and 
drinking is not softened. III 
(118) Facilities with plans approved on or 
after January 1, 1999, shall ensure that the 
entire electrical system and its maintenance 
and operation comply with the 1996 National 
Electrical Code , which is incorporated by 
reference in this rule. Facilities whose plans 
were approved on or before December 31, 
1998, shall comply with the National Electri-
cal Code as referenced in the 1985 Life Safety 
Code. II/III 
8 CODE OF STATE REGULATIONS (9/30/08) ROBIN CARNAHAN 
Secretary of State
19 CSR 30-85—DEPARTMENT OF HEALTH AND 
 SENIOR SERVICES Division 30—Division of Regulation and Licensure

(119) Facilities shall adequately light all 
occupied areas as required by the duties per-
formed in that space. II/III 
(120) Residents’ bedrooms shall have a mini-
mum general illumination of ten (10) footcan-
dles, a night-light and a resident’s reading 
light. The outlets for general illumination and 
night-lights shall be switched at the door. III 
(121) Each single-bed resident room shall 
have at least two (2) duplex receptacles. All 
multi-bed resident rooms shall have at least 
one (1) duplex receptacle at the head of each 
bed plus one (1) additional duplex receptacle. 
Facilities shall not place duplex receptacles in 
a manner to cause an electrical shock hazard. 
III 
(122) Facilities shall furnish lighting fixtures 
of a type suitable for the space for all lighting 
outlets. III 
(123) If ceiling lights are used in residents’ 
rooms, they shall be of a type which are shad-
ed or globed to minimize glare. III 
(124) Facilities shall provide an electrically-
powered nurses’ call system with indicator 
lights at the corridor entrance of each bed-
room. Audible signals and indicating panels 
shall be located in each nurses’ station and 
utility room. Facilities shall provide signal 
buttons at the head of each resident bed, in 
each toilet room and in each bathroom. III 
(125) Facilities shall provide night-lights in 
hallways, individual toilet rooms, stairways 
and resident rooms or adjacent toilet rooms. 
II 
(126) A qualified electrician shall test and 
certify the entire electrical system as being in 
compliance with the 1996 National Electrical 
Code, incorporated by reference in this rule. 
In facilities whose plans were approved on or 
before December 31, 1998, the electrician 
shall test the system according to the stan-
dards of the National Electrical Code as ref-
erenced in the 1985 Life Safety Code. Facil-
ities shall make this test certification available 
to the division. III 
(127) Facilities shall provide a complete, 
electrically-operated door alarm system that 
is audible in the nurses’ station for all resi-
dent-accessible exterior doors. III 
(128) A facility shall have emergency light-
ing for exits, stairs, corridors and nurses’ sta-
tions. Facilities may provide this emergency 
lighting using an emergency generator or bat-
tery-operated lights rated at least one and 
one-half (1 1/2) hours. In facilities with 
plans approved on or after January 1, 1999, 
an emergency generator shall supply emer-
gency power to life support systems as 
required by the 1993 NFP A 99, Health Care 
Facilities, incorporated by reference in this 
rule. In facilities where plans were approved 
on or before December 31, 1998, the electri-
cal system shall comply to the standards of 
the National Electrical Code as referenced in 
the 1985 Life Safety Code. III 
(129) The elevator installations shall comply 
with all local and state codes, American 
Standards Association Specification A17.1, 
1993 Safety Code for Elevators and Escala-
tors, the 1996 National Electrical Code , 
incorporated by reference in this rule, and the 
minimum general standards as set forth in 
this rule. In facilities whose plans were 
approved on or before December 31, 1998, 
the elevators shall comply with applicable 
local and state codes and the requirements set 
forth in the ASAS A17.1, Safety Code for 
Elevators and Escalators, and the National 
Electrical Code as referenced in the 1985 Life 
Safety Code. II 
(130) Any facility with residents on one (1) 
or more floors above the first floor shall have 
at least one (1) hydraulic or electric motor 
driven elevator. Facilities with a bed capacity 
from sixty-one to two hundred (61–200) 
above the first floor shall not have less than 
two (2) elevators. II 
(131) Facilities with a bed capacity of from 
two hundred to three hundred fifty (200—
350) above the first floor shall have not less 
than three (3) elevators—two (2) passenger 
and one (1) service. II 
(132) Inside cab dimensions of elevators shall 
be not less than five feet four inches by eight 
feet (5' 4" × 8') with a capacity of three 
thousand five hundred pounds (3,500 lbs.). 
Cab and shaft doors shall have no less than 
three feet ten inches (3' 10") clear opening. 
Elevators for which operators will not be 
employed shall have automatic push-button 
controls, signal controls or dual controls for 
use with or without the operator. Where two 
(2) push-button elevators are located together 
and where one (1) elevator serves more than 
three (3) floors and basement, they shall have 
collective or signal control. III 
(133) Facilities with plans approved on or 
after January 1, 1999, shall have overspeed 
tests conducted on all elevator machines. 
Elevators will be tested for speed and load, 
with and without loads, in both directions as 
covered by the 1993 Safety Code for Eleva-
tors and Escalators , incorporated by refer-
ence in this rule. Facilities whose plans were 
approved on or before December 31, 1998, 
shall conduct overspeed tests in accordance 
with applicable local and state codes and the 
requirements set forth in the ASAS A17.1, 
Safety Code for Elevators and Escalators, as 
referenced in the 1985 Life Safety Code. 
Facilities shall make this test certification 
available to the division. III 
AUTHORITY: section 198.009, RSMo Supp. 
1998.* This rule originally filed as 13 CSR 
15-14.012. Original rule filed July 13, 1983, 
effective Oct. 13, 1983. Amended: Filed Aug. 
1, 1988, effective Nov. 1 1, 1988. Amended: 
Filed May 1 1, 1998, effective Dec. 30, 1998. 
Emergency amendment filed May 12, 1999, 
effective May 22, 1999, expired Feb. 24, 
2000. Amended: Filed July 13, 1999, effec-
tive Jan. 30, 2000. Moved to 19 CSR 30-
85.012, effective Aug. 28, 2001. 
*Original authority: 198.009, RSMo 1979, amended 
1993, 1995. 

19 CSR 30-85.022 Fire Safety and Emer-
gency Preparedness Standards for New 
and Existing Intermediate Care and 
Skilled Nursing Facilities 
PURPOSE: This rule establishes fire-safety 
and emergency preparedness requirements for 
new and existing intermediate care and 
skilled nursing facilities. 
PUBLISHER’S NOTE: The secretary of state 
has determined that the publication of the 
entire text of the material which is incorpo-
rated by reference as a portion of this rule 
would be unduly cumbersome or expensive. 
This material as incorporated by reference in 
this rule shall be maintained by the agency at 
its headquarters and shall be made available 
to the public for inspection and copying at no 
more than the actual cost of reproduction. 
This note applies only to the reference mate-
rial. The entire text of the rule is printed 
here. 
AGENCY NOTE: All rules relating to long-
term care facilities licensed by the Depart-
ment of Health and Senior Services are fol-
lowed by a Roman Numeral notation which 
refers to the class (either class I, II, or III) of 
standard as designated in section 198.085, 
RSMo 2000. 
(1) Definitions. For the purpose of this rule, 
the following definitions shall apply: 
 CODE OF STATE REGULATIONS 9JOHN R. ASHCROFT (5/31/20) 
Secretary of State
Chapter 85—Intermediate Care and Skilled Nursing Facility 19 CSR 30-85
(A) Accessible spaces—shall include all 
rooms, halls, storage areas, basements, attics, 
lofts, closets, elevator shafts, enclosed stair-
ways, dumbwaiter shafts, and chutes; 
(B) Area of refuge—a space located in or 
immediately adjacent to a path of travel lead-
ing to an exit that is protected from the 
effects of fire, either by means of separation 
from other spaces in the same building or its 
location, permitting a delay in evacuation. An 
area of refuge may be temporarily used as a 
staging area that provides some relative safety 
to its occupants while potential emergencies 
are assessed, decisions are made, and if 
applicable, evacuation has begun; 
(C) Major renovation—shall include the 
following: 
1. Addition of any room(s), accessible 
by residents, that either exceeds fifty percent 
(50%) of the total square footage of the facil-
ity or exceeds four thousand five hundred 
(4,500) square feet; 
2. Repairs, remodeling, or renovations 
that involve more than fifty percent (50%) of 
the building; 
3. Repairs, remodeling, or renovations 
that involve more than four thousand five 
hundred (4,500) square feet of a smoke sec-
tion; or 
4. If the addition is separated by two- 
(2-) hour fire-resistant construction, only the 
addition portion shall meet the requirements 
for an NFP A 13, 1999 edition, sprinkler sys-
tem, unless the facility is otherwise required 
to meet NFP A 13, 1999 edition; and 
(D) Concealed spaces—shall include areas 
within the building that cannot be occupied or 
used for storage. 
(2) General Requirements. 
(A) All National Fire Protection Associa-
tion (NFP A) codes and standards cited in this 
rule: NFP A 10, Standard for Portable Fire 
Extinguishers, 1998 edition; NFP A 13, Stan-
dard for the Installation of Sprinkler Systems, 
1999 edition; NFP A 96, Standard for Ventila-
tion Control and Fire Protection of Commer-
cial Cooking Operations , 1998 edition; 
NFP A 99, Standard for Health Care Facili-
ties, 1999 edition; NFP A 101, The Life Safety 
Code, 2000 edition; NFP A 72, National Fire 
Alarm Code, 1999 edition; NFP A 25, Stan-
dard for the Inspection, Testing, and Mainte-
nance of Water-Based Fire Protection Sys-
tems, 1998 edition; NFP A 253, Standard 
Method of Test of Surface Burning Character-
istics of Building Materials , 2000 edition; 
NFP A 701, Standard Methods of Fire Tests 
for Flame Propagation of Textiles and Films, 
1999 edition; NFP A 211, Chimneys, Fire-
places, Vents and Solid Fuel-Burning Appli-
ances, 2000 edition; and NFP A 101A, Guide 
to Alternative Approaches to Life Safety , 
2001 edition, are incorporated by reference in 
this rule and available for purchase from the 
National Fire Protection Agency, 1 Battery-
march Park, Quincy, MA 02269- 9101; 
www.nfpa.org; by telephone at (617) 770-
3000 or 1-800-344-3555. This rule does not 
incorporate any subsequent amendments or 
additions to the materials listed above. 
(B) This rule does not prohibit facilities 
from complying with standards set forth in 
newer editions of the incorporated by refer-
ence material listed in subsection (2)(A) of 
this rule if approved by the department. 
(C) The department shall have the right of 
inspection of any portion of a building in 
which a licensed facility is located unless the 
unlicensed portion is separated by two- (2-) 
hour fire-resistant construction. I/II 
(D) Facilities shall not use space under 
stairways to store combustible materials. I/II 
(E) No section of the building shall present 
a fire hazard. I/II 
(F) All facilities shall notify the depart-
ment immediately after the emergency is 
addressed if there is a fire in the facility or 
premises and shall submit a complete written 
fire report to the department within seven (7) 
days of the fire, regardless of the size of the 
fire or the loss involved. II/III 
(G) Following the discovery of any fire, the 
facility shall monitor the area and/or the 
source of the fire for a twenty-four- (24-) 
hour period. This monitoring shall include, at 
a minimum, hourly visual checks of the area. 
These hourly visual checks shall be docu-
mented. I/II 
(H) All electrical appliances shall be 
Underwriters’ Laboratories (UL) or Factory 
Mutual (FM)-approved, shall be maintained 
in good repair, and no appliances or electrical 
equipment shall be used which emit fumes or 
which could in any other way present a haz-
ard to the residents. I/II 
(3) All openings that could permit the passage 
of fire, smoke, or both, between floors shall 
be fire-stopped with a suitable noncom-
bustible material. II/III 
(4) Hazardous areas shall be separated by 
construction of at least one- (1-) hour fire-
resistant construction. Hazardous areas may 
be protected by an automatic sprinkler system 
in lieu of a one- (1-) hour rated fire-resistant 
construction. When the sprinkler option is 
chosen, the areas shall be separated from 
other spaces by smoke-resistant partitions and 
doors. The doors shall be self-closing or 
automatic closing. II 
(5) The sto rage of any unnecessary com-
bustible materials in any part of a building in 
which a licensed facility is located is prohib-
ited. No section of the building shall present 
a fire hazard. I/II 
(6) Oxygen sto rage shall be in accordance 
with NFP A 99, 1999 edition. Facilities shall 
use permanent racks or fasteners to prevent 
accidental damage or dislocation of oxygen 
cylinders. Safety caps shall remain intact 
except where a cylinder is in actual use or 
where the regulator has been attached and the 
cylinder is ready for use. Individual oxygen 
cylinders in use or with an attached regulator 
shall be supported by cylinder collars or by 
stable cylinder carts. II/III 
(7) Each nursing unit may maintain only one 
(1) emergency-use oxygen tank in a readily 
accessible unit area. II 
(8) Fire Extinguishers. 
(A) Fire extinguishers shall be provided at 
a minimum of one (1) per floor, so that there 
is no more than seventy-five feet (75') travel 
distance from any point on that floor to an 
extinguisher. I/II 
(B) All new or replacement portable fire 
extinguishers shall be ABC-rated extinguish-
ers, in accordance with the provisions of 
NFP A 10, 1998 edition. A K-rated extin-
guisher or its equivalent shall be used in lieu 
of an ABC-rated extinguisher in the kitchen 
cooking areas. II 
(C) Fire extinguishers shall have a rating of 
at least— 
1. Ten pounds (10 lbs.), ABC-rated or 
the equivalent, in or within fifteen feet (15') 
of hazardous areas as defined in 19 CSR 30-
83.010; II and 
2. Five pounds (5 lbs.), ABC-rated or 
the equivalent, in other areas. II 
(D) All fire extinguishers shall bear the 
label of the UL or the FM Laboratories and 
shall be installed and maintained in accor-
dance with NFP A 10, 1998 edition. This 
includes the documentation and dating of a 
monthly pressure check. II/III 
(9) Facilities shall provide every cooking 
range with a range hood and approved range 
hood extinguishing system installed, tested, 
and maintained in accordance with NFP A 96, 
1998 edition. The range hood and its extin-
guishing system shall be certified at least 
twice annually in accordance with NFP A 96, 
1998 edition. II/III 
(10) Complete Fire Alarm Systems. 
(A) Facilities shall have a complete fire 
alarm system installed in accordance with 
10 CODE OF STATE REGULATIONS (5/31/20) JOHN R. ASHCROFT 
Secretary of State
19 CSR 30-85—DEPARTMENT OF HEALTH AND 
 SENIOR SERVICES Division 30—Division of Regulation and Licensure

NFP A 101, Section 18.3.4, 2000 edition. 
The complete fire alarm system shall auto-
matically transmit to the fire department, dis-
patching agency, or central monitoring com-
pany. The complete fire alarm system shall 
include visual signals and audible alarms that 
can be heard throughout the building and a 
main panel that interconnects all alarm-acti-
vating devices and audible signals in accor-
dance with NFP A 72, 1999 edition. Manual 
pull stations shall be installed at or near each 
required nurse/attendant’s station and each 
required exit. Smoke detectors shall be inter-
connected to the complete fire alarm system. 
Specific minimum requirements relating to 
the interconnected smoke detectors are found 
in subsections (10)(I) and (10)(J) of this rule. 
I/II 
(B) All facilities shall test and maintain the 
complete fire alarm system in accordance 
with NFP A 72, 1999 edition. I/II 
(C) All facilities shall have inspections and 
written certifications of the complete fire 
alarm system completed by an approved qual-
ified service representative in accordance 
with NFP A 72, 1999 edition, at least annual-
ly. I/II 
(D) The complete fire alarm system shall 
be activated by all of the following: sprinkler 
system flow alarm, smoke detectors, heat 
detectors, manual pull stations, and activation 
of the range hood extinguishment system. 
II/III 
(E) Facilities shall test by activating the 
complete fire alarm system at least once a 
month. II/III 
(F) Facilities shall maintain a record of the 
complete fire alarm system tests, inspections 
and certifications required by subsections 
(10)(B), (10)(C), and (10)(E) of this rule. III 
(G) Upon discovery of a fault with the 
complete fire alarm system, the facility shall 
correct the fault. I/II 
(H) When a complete fire alarm system is 
to be out-of-service for more than four (4) 
hours in a twenty-four- (24-) hour period, the 
facility shall immediately notify the depart-
ment and the local fire authority and imple-
ment an approved fire watch in accordance 
with NFP A 101, 2000 edition, until the fire 
alarm system has returned to full service. I/II 
(I) All facilities shall have smoke detectors 
interconnected to the complete fire alarm sys-
tem in all corridors and spaces open to corri-
dors. Smoke detectors shall be no more than 
thirty feet (30') apart with no point on the 
ceiling more than twenty-one feet (21') from 
a smoke detector. I/II 
(J) Facilities that have a sprinkler system 
exemption shall have smoke detectors inter-
connected to the complete fire alarm system 
in all accessible spaces within the facility as 
required by NFP A 72, 1999 edition. Smoke 
detectors shall be no more than thirty feet 
(30') apart with no point on the ceiling more 
than twenty-one feet (21') from a smoke 
detector. Smoke detectors shall not be 
installed in areas where environmental influ-
ences may cause nuisance alarms. Such areas 
include, but are not limited to, kitchens, laun-
dries, bathrooms, mechanical air handling 
rooms, and attic spaces. In these areas, heat 
detectors interconnected to the complete fire 
alarm system shall be installed. Bathrooms 
not exceeding fifty-five (55) square feet and 
clothes closets, linen closets, and pantries not 
exceeding twenty-four (24) square feet are 
exempt from having any detection device if 
the walls and ceilings are surfaced with limit-
ed-combustible or noncombustible material 
as defined in NFP A 101, 2000 edition. Con-
cealed spaces of noncombustible or limited-
combustible construction are not required to 
have detection devices. These spaces may 
have limited access but cannot be occupied or 
used for storage. I/II 
(K) For each facility not having a sprinkler 
system exemption, each resident room or any 
room designated for sleeping shall be 
equipped with at least one (1) battery-powered 
smoke alarm installed, tested, and maintained 
in accordance with manufacturer’s specifica-
tions. In addition, the facility shall be 
equipped with interconnected heat detectors 
installed, tested, and maintained in accor-
dance with NFP A 72, 1999 edition, with 
detectors in all areas subject to nuisance 
alarms, including, but not limited to, kitchens, 
laundries, bathrooms, mechanical air handling 
rooms,
 and attic spaces. I/II 
1. The facility shall maintain a written 
record of the monthly testing and battery 
changes. The written records shall be 
retained for one (1) year. I/II 
2. Upon discovery of a fault with any 
detector or alarm, the facility shall correct 
the fault. I/II 
(11) Sprinkler System. 
(A) All facilities shall have inspections and 
written certifications of the sprinkler system 
completed by an approved qualified service 
representative in accordance with NFP A 25, 
1998 edition. The inspections shall be in 
accordance with the provisions of NFP A 25, 
1998 edition, with certification at least annu-
ally by a qualified service representative. I/II 
(B) All facilities licensed prior to August 
28, 2007, that were not required to have a 
complete sprinkler system in accordance with 
NFP A 13 shall have until December 31, 
2012, to comply with NFP A 13, 1999 edi-
tion. I/II 
1. Exemptions shall be granted if the 
facility presents evidence in writing from a 
certified sprinkler system representative or 
licensed engineer that the facility is unable to 
install an approved NFP A 13, 1999 edition, 
system due to the unavailability of the water 
supply. I/II 
(C) Facilities that have a sprinkler system 
installed prior to August 28, 2007, shall 
inspect, maintain, and test these systems in 
accordance with the requirements in effect 
for such facilities on August 27, 2007. I/II 
(D) Facilities licensed on or after August 
28, 2007, or any section of a facility in which 
a major renovation has been completed on or 
after August 28, 2007, shall install and main-
tain a complete sprinkler system in accor-
dance with NFP A 13, 1999 edition. I/II 
(E) When a sprinkler system is to be out-
of-service for more than four (4) hours in a 
twenty-four- (24-) hour period, the facility 
shall immediately notify the department and 
the local fire authority and implement an 
approved fire watch in accordance with 
NFP A 101, 2000 edition, until the sprinkler 
system has returned to full service. I/II 
(12) Each floor of an existing licensed facility 
shall have at least two (2) unobstructed exits 
remote from each other. One (1) of the 
required exits in an existing multi-story facil-
ity must be an outside stairway or an enclosed 
stair that is separated by one- (1-) hour con-
struction from each floor and has an exit 
leading directly outside at grade level. One 
(1) exit may lead to a lobby with exit facilities 
to the ground level outside instead of leading 
directly to the outside. The lobby shall have 
at least a one- (1-) hour fire-rated separation 
from the remainder of the exiting floor. I/II 
(13) If facilities have outside stairways, they 
shall be substantially constructed to support 
residents during evacuation. These stairways 
shall be protected or cleared of ice and snow. 
Stairways shall be of sturdy construction 
using at least two-inch (2") lumber and shall 
be continuous to ground level. All treads and 
risers shall be of the same height and width 
throughout the entire stairway, not including 
landings. II/III 
(14) Fire escapes added to existing buildings, 
whether interior or exterior, shall have at 
least a minimum thirty-six-inch (36") width, 
eight-inch (8") maximum risers, a nine-inch 
(9") minimum tread, no winders, a maximum 
height between landings of twelve feet (12'), 
minimum landing dimensions of forty-four 
inches (44"), landings at each exit door, and 
handrails on both sides. Exit(s) to fire 
escapes shall be at least thirty-six inches 
(36") wide, and the fire-escape door shall 
 CODE OF STATE REGULATIONS 11JOHN R. ASHCROFT (5/31/20) 
Secretary of State
Chapter 85—Intermediate Care and Skilled Nursing Facility 19 CSR 30-85
swing outward. All treads and risers shall be 
of the same height and width throughout the 
entire stairway, not including landings. II/III 
(15) Facilities with three (3) or more floors 
shall comply with the provisions of Chapter 
320, RSMo, which requires that outside 
stairways be constructed of iron or steel. II 
(16) Door locks shall be of a type that can be 
opened from the inside by turning the knob or 
operating a simple device that will release the 
lock, or shall meet the requirements of Sec-
tion 19.2 of NFP A 101, 2000 edition. Only 
one (1) lock will be permitted on any one (1) 
door. I/II 
(17) All exit doors in existing licensed facili-
ties shall be at least thirty inches (30") wide. 
II 
(18) All exit doors in new facilities shall be at 
least forty-four inches (44") wide. II 
(19) In all facilities, all exit doors and 
vestibule doors shall swing outward in the 
direction of exit travel. II 
(20) In all existing licensed facilities, all hor-
izontal exit doors in fire walls and all doors 
in smoke barrier partitions may swing in 
either direction. These doors normally may 
be open, but shall be automatically self-clos-
ing upon activation of the fire alarm system. 
They shall be capable of being manually 
released to self-closing action. II/III 
(21) Facilities shall maintain corridors to be 
free of obstruction, equipment, or supplies 
not in use. Doors to resident rooms shall not 
swing into the corridor. II/III 
(22) Facilities shall place signs bearing the 
word EXIT in plain, legible block letters at 
each required exit, except at doors directly 
from rooms to exit corridors or passageways. 
II 
(23) Wherever necessary, the facility shall 
place additional signs in corridors and pas-
sageways to indicate the exit’s direction. Let-
ters on these signs shall be at least six inches 
(6") high and principle strokes three-fourths 
inch (3/4") wide, except that the letters of 
internally illuminated exit signs may be not 
less than four inches (4") high. III 
(24) Facilities shall maintain all exit and 
directional signs to be clearly legible and 
electrically illuminated at all times by accept-
able means such as emergency lighting when 
lighting fails. II 
(25) Facilities shall have emergency lighting 
of sufficient intensity to provide for the safety 
of residents and other people using any exit, 
stairway, and corridor. The lighting shall be 
supplied by an emergency service, an auto-
matic emergency generator or battery lighting 
system. This emergency lighting system shall 
be equipped with an automatic transfer 
switch. In an existing licensed facility, battery 
lights, if used, shall be wet cell units or other 
rechargeable-type batteries that shall be UL-
approved and capable of operating the light 
for at least one and one-half (1 ½) hours. 
Battery-operated emergency lighting shall be 
tested for at least thirty (30) seconds every 
thirty (30) days, and an annual function test 
shall be conducted for the full operational 
duration of one and one-half (1 ½) hours. 
Records of these tests shall be documented 
and maintained for review. II 
(26) If existing licensed facilities have laun-
dry chutes, dumbwaiter shafts, or other simi-
lar vertical shafts, they shall have a fire resis-
tance rating of at least one (1) hour if serving 
three (3) or fewer stories. Enclosures serving 
four (4) or more stories shall have at least a 
two- (2-) hour fire-rated enclosure. These 
chute or shaft doors shall be self-closing or 
shall have any other approved device that will 
guarantee separation between floors. II 
(27) Existing licensed multistoried facilities 
shall provide a smoke separation barrier 
between the basement and the first floor and 
the floors of resident-use areas. At a mini-
mum, this barrier shall consist of one-half 
inch (1/2") gypsum board, plaster, or equiv-
alent. There shall be a one and three-fourths 
inch (1 3/4") thick solid-core wood door, or 
equivalent, at the top or bottom of the stairs. 
If the door is glazed, it shall be glazed with 
wired glass. II 
(28) Each floor accessed by residents shall be 
divided into at least two (2) smoke sections 
with each section not exceeding one hundred 
fifty feet (150') in length or width. If the 
floor’s dimensions do not exceed seventy-five 
feet (75') in length or width, a division of the 
the floor into two (2) smoke sections will not 
be required. II 
(29) Each smoke section shall be separated by 
one- (1-) hour fire-rated walls that are contin-
uous from outside wall-to-outside wall and 
from floor-to-floor or floor-to-roof deck. All 
doors in this wall shall be at least twenty- 
(20-) minute fire rated or its equivalent, self-
closing, and may be held open only if the 
door closes automatically upon activation of 
the fire alarm system. II 
(30) Existing licensed facilities shall have 
attached self-closing devices on all doors pro-
viding separation between floors. If the doors 
are to be held open, they shall have electro-
magnetic hold-open devices that are intercon-
nected with either a smoke alarm or with 
other smoke-sensitive fire extinguishment or 
alarm systems in the building. II/III 
(31) Smoking shall be permitted only in des-
ignated areas. Areas where smoking is per-
mitted shall be directly supervised unless the 
resident has been assessed by the facility and 
determined capable of smoking unassisted. 
At least annually, the facility shall reassess 
those residents the facility has determined to 
be capable of smoking unsupervised and shall 
also reassess such resident when changes in 
his or her condition indicate the resident may 
no longer be capable of smoking without 
supervision. The facility shall document this 
assessment in the resident’s medical record. 
II 
(32) Designated smoking areas shall have 
ashtrays of noncombustible material and of 
safe design. The contents of ashtrays shall be 
disposed of properly in receptacles made of 
noncombustible material. II/III 
(33) 
Fire Drills and Emergency Preparedness. 
(A) All facilities shall have a written plan 
to meet potential emergencies or disasters 
and shall request consultation and assistance 
annually from a local fire unit for review of 
fire and evacuation plans. If the consultation 
cannot be obtained, the facility shall inform 
the state fire marshal in writing and request 
assistance in review of the plan. An up-to-
date copy of the facility’s entire plan shall be 
provided to the local jurisdiction’s emergency 
management director. II/III 
(B) The plan shall include, but is not lim-
ited to— 
1. A phased response ranging from relo-
cation of residents to an immediate area with-
in the facility; relocation to an area of refuge, 
if applicable; or to total building evacuation. 
This phased response part of the plan shall be 
consistent with the direction of the local fire 
unit or state fire marshal and shall be appro-
priate for the fire or emergency; 
2. Written instructions for evacuation of 
each floor including evacuation to areas of 
refuge, if applicable, and floor plan showing 
the location of exits, fire alarm pull stations, 
fire extinguishers, and any areas of refuge; 
3. Evacuating residents, if necessary, 
from an area of refuge to a point of safety 
outside the building; 
4. The location of any additional water 
sources on the property such as cisterns, 
12 CODE OF STATE REGULATIONS (5/31/20) JOHN R. ASHCROFT 
Secretary of State
19 CSR 30-85—DEPARTMENT OF HEALTH AND 
 SENIOR SERVICES Division 30—Division of Regulation and Licensure

wells, lagoons, ponds, or creeks; 
5. Procedures for the safety and comfort 
of residents evacuated; 
6. Staffing assignments; 
7. Instructions for staff to call the fire 
department or other outside emergency ser-
vices; 
8. Instructions for staff to call alterna-
tive resource(s) for housing residents, if nec-
essary; 
9. Administrative staff responsibilities; 
and 
10. Designation of a staff member to be 
responsible for accounting for all residents’ 
whereabouts. II/III 
(C) The written plan shall be accessible at 
all times and an evacuation diagram shall be 
posted on each floor in a conspicuous place 
so that employees and residents can become 
familiar with the plan and routes to safety. 
II/III 
(D) A minimum of twelve (12) fire drills 
shall be conducted annually with at least one 
(1) every three (3) months on each shift. At 
least four (4) of the required fire drills must 
be unannounced to residents and staff, 
excluding staff who are assigned to evaluate 
staff and resident response to the fire drill. 
The fire drills shall include a simulated resi-
dent evacuation that involves the local fire 
department or emergency service at least 
once a year. II/III 
(E) The fire alarm shall be activated during 
all fire drills unless the drill is conducted 
between 9 p.m. and 6 a.m., when a facility-
generated predetermined message is accept-
able in lieu of the audible and visual compo-
nents of the fire alarm. II/III 
(F) The facility shall keep a record of all 
fire drills including the simulated resident 
evacuation. The record shall include the time, 
date, personnel participating, length of time 
to complete the fire drill, and a narrative 
notation of any special problems. III 
(34) Fire Safety Training Requirements. 
(A) The facility shall ensure that fire safety 
training is provided to all employees: 
1. During employee orientation; 
2. At least every six (6) months; and 
3. When training needs are identified as 
a result of fire drill evaluations. II/III 
(B) The training shall include, but is not 
limited to, the following: 
1. Prevention of fire ignition, detection 
of fire, and control of fire development; 
2. Confinement of the effects of fire; 
3. Procedures for moving residents to an 
area of refuge, if applicable; 
4. Use of alarms; 
5. Transmission of alarms to the fire 
department; 
6. Response to alarms; 
7. Isolation of fire; 
8. Evacuation of the immediate area and 
building; 
9. Preparation of floors and facility for 
evacuation; and 
10. Use of the evacuation plan required 
by section (33) of this rule. II/III 
(35) The use of wood- or gas-burning fire-
places will be permitted only if the fireplaces 
are built of firebrick or metal, enclosed by 
masonry, and have metal or tempered glass 
screens. The chimneys shall be of masonry 
construction with flue linings that have at 
least eight inches (8") of masonry separating 
the flue lining and the fireplace from any 
combustible material. All fireplaces shall be 
installed, operated, and maintained in a safe 
manner. Fireplaces not in compliance with 
these requirements may be provided if they 
are for decorative purposes only or if they are 
equipped with decorative-type electric logs or 
other electric heaters which bear the UL label 
and are constructed of electrical components 
complying with and installed in compliance 
with the National Electrical Code , incorpo-
rated by reference in this rule. Fireplaces 
meeting standards set forth in NFP A 211, 
2000 edition, are considered in compliance 
with this rule. II/III 
(36) All electric or gas clothes dryers shall be 
vented to the outside and the lint trap cleaned 
regularly. II/III 
(37) In existing licensed facilities, all wall 
and ceiling surfaces shall be smooth and free 
of highly-combustible materials. II/III 
(38) All curtains in resident-use areas shall be 
rendered and maintained flame-resistant in 
accordance with NFP A 701, 1999 edition. 
II/III 
(39) All new floor covering installed in build-
ings that do not have a sprinkler system shall 
be Class I in accordance with NFP A 253, 
2000 edition. II/III 
(40) Trash and Rubbish Disposal Require-
ments. 
(A) Only metal or UL- or FM-approved 
wastebaskets shall be used for the collection 
of trash. II 
(B) The facility shall maintain the exterior 
premises in a manner as to provide for fire 
safety. II 
(C) Trash shall be removed from the 
premises as often as necessary to prevent fire 
hazards and public health nuisance. II 
(D) No trash shall be burned within fifty 
feet (50') of any facility except in an approved 
incinerator. I/II 
(E) Trash may be burned only in a mason-
ry or metal container. The container shall be 
equipped with a metal cover with openings no 
larger than one-half inch (1/2") in size. II/III 
(41) Minimum Staffing for Safety and Protec-
tive Oversight to Residents. 
(A) In a building that is of fire-resistant 
construction or a building with a sprinkler 
system, minimum staffing shall be the follow-
ing: 
 
 Time Personnel Residents 
7 a.m. to 3 p.m. 1 3–10* 
 (Day) 
3 p.m. to 11 p.m. 1 3–15* 
 (Evening) 
11 p.m. to 7 a.m. 1 3–20* 
 (Night) 
*One (1) additional staff person for every 
fraction after that. I/II 
(B) In a building that is of nonfire-resistant 
construction or a building that has a sprinkler 
system exemption, minimum staffing shall be 
the following: 
 
 Time Personnel Residents 
7 a.m. to 3 p.m. 1 3–10* 
 (Day) 
3 p.m. to 11 p.m. 1 3–15* 
 (Evening) 
11 p.m. to 7 a.m. 1 3–15* 
 (Night) 
*One (1) additional staff person for every 
fraction after that. I/II 
AUTHORITY: sections 198.074 and 198.079, 
RSMo Supp. 201 1.* This rule originally filed 
as 13 CSR 15-14.022. Original rule filed July 
13, 1983, effective Oct. 13, 1983. Amended: 
Filed Sept. 12, 1984, effective Dec. 13, 1984. 
Amended: Filed Aug. 1, 1988, effective Nov. 
1 1, 1988. Amended: Filed May 1 1, 1998, 
effective Dec. 30, 1998. Emergency amend-
ment filed May 12, 1999, effective May 22, 
1999, expired Feb. 24, 2000. Amended: Filed 
July 13, 1999, effective Jan. 30, 2000. Moved 
to 19 CSR 30-85.022, effective Aug. 28, 2001. 
Emergency amendment filed Nov. 24, 2008, 
effective Dec. 4, 2008, expired June 1, 2009. 
Amended: Filed Nov. 24, 2008, effec
tive May 
30, 2009. Amended: Filed March 15, 2012, 
effective Oct. 30, 2012. ** 
*Original authority: 198.074, RSMo 2007 and 198.079, 
RSMo 1979, amended 2007. 
**Pursuant to Executive Order 21-07, 19 CSR 30-85.022, sections 
 CODE OF STATE REGULATIONS 13JOHN R. ASHCROFT (11/30/21) 
Secretary of State
Chapter 85—Intermediate Care and Skilled Nursing Facility 19 CSR 30-85
(8) and (9) and subsections (10)(C) and (1 1)(A) was suspended from 
April 15, 2020 through May 1, 2021. Pursuant to Executive Order 
21-09, 19 CSR 30-85.022, subsection (33)(D) was suspended from 
April 15, 2020 through December 31, 2021. 

19 CSR 30-85.032 Physical Plant Require-
ments for New and Existing Intermediate 
Care and Skilled Nursing Facilities 
PURPOSE: This rule establishes the require-
ments necessary in new and existing interme-
diate care and skilled nursing facilities. 
PUBLISHER’S NOTE: The secretary of state 
has determined that the publication of the 
entire text of the material which is incorpo-
rated by reference as a portion of this rule 
would be unduly cumbersome or expensive. 
This material as incorporated by reference in 
this rule shall be maintained by the agency at 
its headquarters and shall be made available 
to the public for inspection and copying at no 
more than the actual cost of reproduction. 
This note applies only to the reference mate-
rial. The entire text of the rule is printed 
here. 
AGENCY NOTE: All rules relating to long-
term care facilities licensed by the Division of 
Aging are followed by a Roman Numeral 
notation which refers to the class (either class 
I, II or III) of standard as designated in sec-
tion 198.085.1, RSMo. 
(1) General Requirements. 
(A) All National Fire Protection Associa-
tion (NFP A) codes and standards cited in this 
rule: NFP A 54, National Fuel Code , 1999 
edition; NFP A 58, Liquefied Petroleum Gas 
Code, 1999 edition; NFP A 70, National Elec-
tric Code , 1999 edition; NFP A 99, Health 
Care Facilities, 1999 edition; and NFP A 101, 
The Life Safety Code , 2000 edition, are 
incorporated by reference in this rule and 
available for purchase from the National Fire 
Protection Agency, 1 Batterymarch Park, 
Quincy, MA 02269-9101; www.nfpa.org; by 
telephone at (617) 770-3000 or 1-800-344-
3555. This rule does not incorporate any sub-
sequent amendments or additions to the mate-
rials listed above. 
(B) This rule does not prohibit facilities 
from complying with standards set forth in 
newer editions of the incorporated by refer-
ence material listed in subsection (1)(A) of 
this rule where approved by the Department 
of Health and Senior Services (the depart-
ment). 
(2) The building shall be substantially con-
structed and shall be maintained in good 
repair. New facilities shall comply with the 
requirements in accordance with the provi-
sions found in 19 CSR 30-85.012. Existing 
licensed facilities shall meet and maintain the 
facility’s physical plant in accordance with 
the construction standards in effect at the 
time of initial licensing, unless there is a spe-
cific rule governing the subject cited in this 
section or in 19 CSR 30-85.022, except that 
those facilities licensed between 1957 and 
1965 shall not increase the capacity of any 
room or the total capacity of the facility with-
out meeting new construction requirements. 
Existing licensed facilities with plans 
approved after April 8, 1972 and prior to Jan-
uary 1, 1999, shall comply as Existing 
Health Care Occupancies with NFP A 101, 
2000 edition. Facilities whose physical plant 
requirement plans are approved on or after 
January 1, 1999, shall comply as New Health 
Care Occupancies with NFP A 101, 2000 edi-
tion. II/III 
(3) In an existing facility licensed prior to 
July 1, 1965, the number of persons in any 
room or area used as sleeping quarters shall 
not exceed the proportion of one (1) adult for 
each sixty (60) square feet. In facilities 
licensed on or after July 1, 1965, adult resi-
dent rooms shall be a minimum of eighty (80) 
square feet per bed in multi-bed resident 
rooms and one hundred (100) square feet for 
private rooms. This square footage can 
include all useable floor spaces such as clos-
ets, entryways, and areas with moveable 
items or furniture that do not impact the safe-
ty or welfare of the resident, used for resi-
dents’ belongings or if related to their care. 
Only the area of a room with a ceiling height 
of at least seven feet (7') can be included 
when calculating the square footage. II/III 
(4) An existing facility licensed prior to July 
1, 1965 shall not use a private room less than 
sixty (60) square feet in size as sleeping quar-
ters for residents under seventeen (17) years 
of age. In multi-bed resident rooms, the fol-
lowing ratios shall apply: thirty (30) square 
feet per bed for beds four feet (4') or less in 
length, forty (40) square feet per bed for beds 
four feet through five feet (4'–5') in length 
and sixty (60) square feet per bed for beds 
over five feet (5') in length. In facilities 
licensed on or after July 1, 1965, rooms shall 
be a minimum of thirty-five (35) square feet 
per bed for beds four feet (4') or less in 
length; forty-five (45) square feet per bed for 
beds four feet through five feet (4'–5') in 
length; eighty (80) square feet per bed over 
five (5) square feet in length in multiple bed-
rooms; and one hundred (100) square feet for 
private rooms. II/III 
(5) A facility may not house a resident in a 
room which has an outside grade of more 
than three feet (3') above the floor level on 
the window side of the resident’s room for a 
distance of at least fifteen feet (15') from the 
outside wall of the resident’s room. II/III 
(6) Facilities initially licensed after July 1, 
1965 shall have no more than four (4) beds 
per room. II/III 
(7) The facility shall provide sleeping quar-
ters, separate from resident bedrooms for the 
administrator or employees and their families 
who reside there. III 
(8) A facility shall conspicuously and unmis-
takably identify each room or ward or resi-
dent-use area with a number or room name 
securely fastened to, or plainly painted on the 
entrance of the room or ward. III 
(9) Each resident room shall have an outside 
window with an area equivalent to not less 
than ten percent (10%) of the required floor 
area. The facility shall maintain windows so 
that they may be readily opened and closed. 
II/III 
(10) Facilities shall ensure that every window 
in resident-use areas has shades, curtains or 
drapes. III 
(11) The facility shall make provisions for a 
room(s) which can be used for isolation of a 
resident(s) with communicable diseases. 
Facilities licensed after July 1, 1965 and 
prior to June 11, 1981 shall have at least two 
(2) private rooms with a toilet room equipped 
with toilet and handwashing sink. Rooms des-
ignated as isolation rooms may be occupied 
by residents provided there is a written agree-
ment on file indicating the resident’s willing-
ness to relocate without prior notice if the 
room is needed for isolation purposes. III 
(12) Every facility shall provide a living room 
or community room for the sole use of resi-
dents. Sufficient chairs and tables shall be 
furnished. Under no circumstances may the 
living room be used as a bedroom. A living 
room must be well-lighted, ventilated, and 
easily accessible to residents. II 
(13) Facilities shall ensure that gas-burning 
equipment and appliances are approved by 
the American Gas Association and installed 
in compliance with NFP A 54, 1999 edition . 
Where liquefied petroleum gas (LPG) is 
used, facilities shall comply with the rules of 
the Missouri Department of Agriculture and 
NFP A 58, 1999 edition. Facilities that were 
complying prior to the effective date of this 
rule with prior editions of the NFP A 54 and 
NFP A 58 referenced in this rule shall be per-
mitted to continue to comply with the earlier 
editions, as long as there is not an imminent 
14 CODE OF STATE REGULATIONS (11/30/21) JOHN R. ASHCROFT 
Secretary of State
19 CSR 30-85—DEPARTMENT OF HEALTH AND 
 SENIOR SERVICES Division 30—Division of Regulation and Licensure

 CODE OF STATE REGULATIONS 15JOHN R. ASHCROFT (11/30/21) 
Secretary of State
Chapter 85—Intermediate Care and Skilled Nursing Facility 19 CSR 30-85
danger to the health, safety, or welfare of any 
resident or a substantial probability that death 
or serious physical harm would result as 
determined by department. Gas-fired water 
heaters shall be properly vented and all water 
heaters shall be equipped with a temperature 
and pressure relief valve. II 
(14) Oxygen cylinders for medical use shall 
be labeled “Oxygen.” All facilities shall have 
oxygen systems, oxygen piping, outlets, man-
ifold rooms, and sto rage rooms installed in 
accordance with the requirements of the 
NFP A 99, 1999 edition. I/II 
(15) Facilities shall provide adequate sto rage 
areas for food, supplies, linen, equipment 
and residents’ personal possessions. II/III 
(16) Toilet rooms shall be easily accessible, 
conveniently located, well-lighted and prop-
erly ventilated. Doors to toilet rooms which 
may be locked from the inside, shall be 
equipped with a special lock which may be 
opened from the outside. II/III 
(17) Existing licensed facilities shall provide 
one (1) toilet for each ten (10) residents or 
fraction of ten. II/III 
(18) The facility shall provide separate toilet 
facilities for each sex. Where urinals are pro-
vided for men, a facility shall provide one (1) 
toilet and urinal for each fifteen (15) males or 
fraction of fifteen. III 
(19) Facilities shall provide grab bars on at 
least one (1) side of all toilets, in proper posi-
tions to facilitate bodily movement of resi-
dents. II 
(20) Existing licensed facilities shall provide 
handwashing facilities consisting of a hand-
washing sink in each toilet room for each fif-
teen (15) residents or fraction of fifteen. The 
handwashing sink may be omitted from a toi-
let room which serves adjacent resident 
rooms if each room contains a handwashing 
sink. II/III 
(21) The facility shall provide one (1) shower 
or tub for each fifteen (15) residents or frac-
tion of fifteen. II/III 
(22) Facilities shall have metal grab bars 
securely mounted for bathtubs, shower stalls 
and toilets. The facility shall also provide 
rubber or similar type nonskid mats or strips 
in tubs and showers to reduce or prevent slip-
ping accidents and hazardous conditions. II 
(23) Facilities shall provide fixed partitions or 
curtains in bathrooms and toilet areas to 
ensure privacy. III 
(24) The facility shall ensure that plumbing 
fixtures that supply hot water and are acces-
sible to the residents, shall be thermostatical-
ly controlled so the water temperature at the 
fixture does not exceed one hundred twenty 
degrees Fahrenheit (120°F) (49°C). The 
water shall be at a temperature range of one 
hundred five degrees Fahrenheit to one 
hundred twenty degrees Fahrenheit (105°F–
120°F) (41°C–49°C). I/II 
(25) Facilities shall provide adequate space 
and locations for the proper cleansing, disin-
fection, sterilization, and sto rage of nursing 
supplies and equipment. This area shall be 
specifically designated as a clean utility area. 
There shall be a separate area designated as a 
dirty utility area, and neither area shall be 
located in or open into a kitchen, dining 
room, or a bathroom. The facility shall have 
utility areas that are easily available to per-
sonnel and located conveniently for the nurs-
ing station staff. Utility areas shall be well-
ventilated and well-lighted. II/III 
(26) The facility shall provide either a nurs-
ing station or a nurses’ work area on each 
floor of a multistory facility. This area shall 
have chart storage space on current residents. 
Facilities licensed or with plans approved on 
or after July 1, 1965, shall have a nurses’ sta-
tion for every sixty (60) beds. Handwashing 
facilities at or near the nurses’ station shall be 
available for physicians, nurses and other per-
sonnel attending residents. II/III 
(27) The facility shall be equipped with a call 
system that consists of an electrical intercom-
munication system, a wireless pager system, 
a buzzer system, or hand bells for each resi-
dent bed, toilet room, and bathroom. The call 
system shall be audible in the attendant’s 
work area and be in compliance with 19 CSR 
30-85.012(124). II/III 
(28) The heating of the building shall be 
restricted to steam, hot water, permanently 
installed electric heating devices or warm air 
systems employing either central heating 
plants with installation so as to safeguard the 
inherent fire hazard or outside wall heaters 
with approved installation. Portable heater 
use is prohibited. Facilities shall provide ade-
quate guards to safeguard residents where 
potential burn hazards exist. I/II 
(29) The facility shall heat all resident-acces-
sible areas to ensure that the air temperature 
is not lower than sixty-eight degrees Fahren-
heit (68°F). These areas shall be capable of 
being heated to not less than eighty degrees 
Fahrenheit (80°F). At all times the reason-
able comfort needs of residents shall be met. 
I/II 
(30) The facility shall cool resident-accessi-
ble areas when air temperatures exceed 
eighty-five degrees Fahrenheit (85°F). These 
areas shall be capable of being cooled to at 
least seventy-one degrees Fahrenheit (71°F). 
At all times the reasonable comfort needs of 
residents shall be met. I/II 
(31) Electrical Wiring Requirements. 
(A) Electrical wiring and equipment shall 
be installed and maintained in accordance 
with the NFP A 70, 1999 edition. Facilities 
that were complying prior to the effective 
date of this rule with prior editions of the 
NFP A 70 referenced in this rule shall be per-
mitted to continue to comply with the earlier 
editions, as long as there is not an imminent 
danger to the health, safety, or welfare of any 
resident or a substantial probability that death 
or serious physical harm would result as 
determined by the department. II/III 
(B) Every two (2) years, a qualified electri-
cian will be required to certify in writing that 
the electrical system is being maintained and 
operated in accordance with the standards 
outlined by the NFP A 70, 1999 edition or the 
earlier NFP A 70 edition with which the facil-
ity was complying prior to the effective date 
of this rule. II/III 
(32) Lighting in hallways, bathrooms, recre-
ational, dining, and all resident-use areas 
shall be provided with a minimum intensity 
of ten (10) footcandles and shall be sufficient 
to meet the residents’ and staff needs. III 
(33) Facilities shall use night-lights in hall-
ways, resident rooms, toilet rooms or bath-
rooms and on stairways. II 
(34) The facility shall ensure that a reading 
light is provided for each resident who 
desires to read. III 
(35) To prevent direct glare to residents’ eyes, 
facilities shall ensure that lights in resident-
use areas have a shade or dome. III 
(36) If elevators are used, their installation 
and maintenance shall comply with all local 
and state codes and NFP A 70, 1999 edition. 
II 
(37) If extension cords are used, they must be 
Underwriters Laboratories (UL)-approved or 
shall comply with other recognized electrical 
appliance approval standards and sized to 
carry the current required for the appliance 
used. Only one (1) appliance shall be con-
nected to one (1) extension cord. Only two 
(2) appliances may be served by one (1) 
duplex receptacle. Extension cords shall not 
be placed under rugs, through doorways, or 
located where they are subject to physical 
damage. II/III 
(38) The facility shall maintain furniture and 
equipment in good condition and shall 
replace it if broken, torn, heavily soiled or 
damaged. Rooms shall be designed and fur-
nished so that the comfort and safety of the 
residents are provided for at all times. II/III 
(39) Rooms shall be neat, orderly and 
cleaned daily. II/III 
(40) The facility shall ensure that each resi-
dent shall be provided an individual bed, sin-
gle or twin, in good repair of rigid type. Beds 
shall be at least thirty-six inches (36") wide. 
Double beds of satisfactory construction may 
be provided for married couples. Rollaway, 
metal cots or folding beds shall not be used. 
II/III 
(41) A minimum of three feet (3') shall be 
available between parallel beds. III 
(42) Mattresses shall be clean, in good repair, 
sized to fit the bed and a minimum of four 
inches (4") in thickness to provide comfort. 
II/III 
(43) The facility shall ensure that each bed 
has at least one (1) clean comfortable pillow. 
Extra pillows shall be available to meet the 
needs of the residents. III 
(44) Multi-bed resident rooms shall have 
screens or curtains, either portable or perma-
nently affixed, available and used to provide 
privacy as needed or as requested. III 
(45) Facilities shall provide each resident 
with an individual locker or other suitable 
space for sto rage of clothing and personal 
belongings. III 
(46) The facility shall provide residents with 
an individual rack for towels and washcloths 
unless they are provided with clean wash-
cloths or towels for use each time needed. III 
(47) A comfortable chair shall be available 
for each resident’s use. III 
(48) Only activities necessary to the adminis-
tration of the facility shall be contained in any 
building used as a long-term care facility 
except as follows: 
(A) Related activities may be conducted in 
buildings subject to prior written approval of 
these activities by the department. Examples 
of these activities are home health agencies, 
physician’s office, pharmacy, ambulance ser-
vice, child day care, food service, and outpa-
tient therapy for the elderly or disabled in the 
community; 
(B) Adult day care may be provided for 
four (4) or fewer participants without prior 
written approval of the department if the 
long-term care facility meets the following 
stipulations: 
1. The operation of the adult day care 
business shall not interfere with the care and 
delivery of services to the long-term care res-
idents; 
2. The facility shall only accept partici-
pants in the adult day care program appropri-
ate to the level of care of the facility and 
whose needs can be met; 
3. The facility shall not change the phys-
ical layout of the facility without prior written 
approval of the department; 
4. The facility shall provide a private 
area for adult day care participants to nap or 
rest; 
5. Adult day care participants shall not 
be included in the census, and the number 
shall not be more than four (4) above the 
licensed capacity of the facility; and 
6. The adult day care participants, while 
on-site, are to be included in the determina-
tion of staffing patterns for the long-term care 
facility; and 
(C) An associated adult day health care 
program may be operated without prior writ-
ten approval if the provider of the adult day 
health care services is certified in accordance 
with 13 CSR 70-92.010. II/III 
AUTHORITY: section 198.079, RSMo Supp. 
2007.* This rule originally filed as 13 CSR 
15-14.032. Original rule filed July 13, 1983, 
effective Oct. 13, 1983. Emergency amend-
ment filed Nov. 9, 1983, effective Nov. 19, 
1983, expired March 18, 1984. Amended: 
Filed Nov. 9, 1983, effective Feb. 1 1, 1984. 
Amended: Filed Sept. 12, 1984, effective 
Dec. 13, 1984. Amended: Filed Aug. 1, 
1988, effective Nov. 1 1, 1988. Amended: 
Filed May 1 1, 1998, effective Dec. 30, 1998. 
Emergency amendment filed Feb. 1, 1999, 
effective Feb. 1 1, 1999, expired Aug. 9, 1999. 
Amended: Filed Feb. 1, 1999, effective July 
30, 1999. Moved to 19 CSR 30-85.032, effec-
tive Aug. 28, 2001. Amended: Filed March 
13, 2008, effective Oct. 30, 2008. ** 
*Original authority: 198.079, RSMo 1979, amended 2007. 
**Pursuant to Executive Order 21-07, 19 CSR 30-85.032, subsection 
(31)(B) was suspended from April 22, 2020 through May 1, 2021 and 
subsection (48)(A) was suspended from April 22, 2020 thr ough 
August 31, 2021. 
19 CSR 30-85.042 Administration and Res-
ident Care Requirements for New and 
Existing Intermediate Care and Skilled 
Nursing Facilities 
PURPOSE: This rule establishes standards 
for administration and resident care in an 
intermediate care or skilled nursing facility. 
Editor’s Note: All rules relating to long-term 
care facilities licensed by the Department of 
Health and Senior Services are followed by a 
roman numeral notation which refers to the 
class (either Class I, II, or III) of standard as 
designated in section 198.085.1, RSMo. 
(1) The operator shall designate a person as 
administrator who holds a current license as 
a nursing home administrator in Missouri. II 
(2) The facility shall post the administrator’s 
license. III 
(3) The operator shall be responsible to 
assure compliance with all applicable laws 
and rules. The administrator shall be fully 
authorized and empowered to make decisions 
regarding the operation of the facility and 
shall be held responsible for the actions of all 
employees. The administrator’s responsibili-
ties shall include the oversight of residents to 
assure that they receive appropriate nursing 
and medical care. II/III 
(4) The administrator shall be employed in 
the facility and serve in that capacity on a 
full-time basis. An administrator cannot be 
listed or function as an administrator in more 
than one (1) licensed facility at the same 
time, except that one (1) administrator may 
serve as the administrator of more than one 
(1) licensed facility if all facilities are on the 
same premises. II/III 
(5) The licensed administrator shall not leave 
the premises without delegating the necessary 
authority in writing to a responsible individ-
ual. If the administrator is absent from the 
facility for more than thirty (30) consecutive 
days, the person designated to be in adminis-
trative charge shall be a currently licensed 
nursing home administrator. Such thirty (30) 
consecutive-day absences may only occur 
once within any consecutive twelve (12)-
month period. I/II 
(6) The facility shall not knowingly admit or 
continue to care for residents whose needs 
cannot be met by the facility directly or in 
cooperation with outside resources. Facilities 
which retain residents needing skilled nursing
16 CODE OF STATE REGULATIONS (11/30/21) JOHN R. ASHCROFT 
Secretary of State
19 CSR 30-85—DEPARTMENT OF HEALTH AND 
 SENIOR SERVICES Division 30—Division of Regulation and Licensure

 CODE OF STATE REGULATIONS 17JOHN R. ASHCROFT (11/30/21) 
Secretary of State
Chapter 85—Intermediate Care and Skilled Nursing Facility 19 CSR 30-85
care shall provide licensed nurses for these 
procedures. I/II 
(7) When outside resources are used to pro-
vide services to the resident, the facility shall 
enter into a written agreement with each 
resource. III 
(8) Persons under seventeen (17) years of age 
shall not be admitted as residents to the facil-
ity unless the facility cares primarily for res-
idents under seventeen (17) years of age. III 
(9) The facility shall not care for more resi-
dents than the number for which the facility 
is licensed. II 
(10) The facility’s current license shall be 
readily visible in a public area within the 
facility. Notices provided to the facility by the 
Division of Aging granting exceptions to reg-
ulatory requirements shall be posted with the 
facility’s license. III 
(11) Regular daily visiting hours shall be 
established and posted. Relatives or 
guardians and clergy, if requested by the res-
ident or family, shall be allowed to see criti-
cally ill residents at any time unless the physi-
cian orders otherwise in writing. II/III 
(12) A supervising physician shall be avail-
able to assist the facility in coordinating the 
overall program of medical care offered in the 
facility. II 
(13) The facility shall develop policies and 
procedures applicable to its operation to 
insure the residents’ health and safety and to 
meet the residents’ needs. At a minimum, 
there shall be policies covering personnel 
practices, admission, discharge, payment, 
medical emergency treatment procedures, 
nursing practices, pharmaceutical services, 
social services, activities, dietary, housekeep-
ing, infection control, disaster and accident 
prevention, residents’ rights and handling 
residents’ property. II/III 
(14) A pharmacist currently licensed in Mis-
souri shall assist in the development of writ-
ten policies and procedures regarding phar-
maceutical services in the facility. II/III 
(15) All personnel shall be fully informed of 
the policies of the facility and of their duties. 
II/III 
(16) All persons who have any contact with 
the residents in the facility shall not knowing-
ly act or omit any duty in a manner which 
would materially and adversely affect the 
health, safety, welfare or property of a resi-
dent. I 
(17) Effective August 28, 1997, each facility 
shall, not later than two (2) working days of 
the date an applicant for a position to have 
contact with residents is hired, request a 
criminal background check, as provided in 
sections 43.530, 43.540 and 610.120, 
RSMo. Each facility must maintain in its 
record documents verifying that the back-
ground checks were requested and the nature 
of the response received for each such 
request. The facility must ensure that any 
applicant who discloses prior to the check of 
his/her criminal records that he/she has been 
convicted of, plead guilty or nolo contendere 
to, or has been found guilty of any A or B 
felony violation of Chapter 565, 566 or 569, 
RSMo, or any violation of subsection 3 of 
section 198.070, RSMo, or of section 
568.020, RSMo, will not be allowed to work 
in contact with patients or residents until and 
unless a check of the applicant’s criminal 
record shows that no such conviction 
occurred. II/III 
(18) The facility must develop and implement 
written policies and procedures which require 
that persons hired for any position which is to 
have contact with any patient or resident have 
been informed of their responsibility to dis-
close their prior criminal history to the facil-
ity as required by section 660.317.5, RSMo. 
The facility— 
(A) Shall also develop and implement poli-
cies and procedures which ensure that the 
facility does not knowingly hire, after August 
28, 1997, any person who has or may have 
contact with a patient or resident, who has 
been convicted of, plead guilty or nolo con-
tendere to, in this state or any other state, or 
has been found guilty of any A or B felony 
violation of Chapter 565, 566 or 569, RSMo, 
or any violation of subsection 3 of section 
198.070, RSMo, or of section 568.020, 
RSMo, unless the person has been granted a 
good cause waiver by the division; 
(B) May consider for employment, in posi-
tions which have contact with resident or 
patients, any person who has been granted a 
good cause waiver by the division in accor-
dance with the provisions of section 660.317, 
RSMo Supp. 1999 and 13 CSR 15-10.060; 
and; 
(C) Shall contact the division to confirm 
the validity of an applicant’s good cause 
waiver prior to hiring the applicant. II/III 
(19) No person who is listed on the employee 
disqualification list maintained by the divi-
sion as required by section 198.070, RSMo 
shall work or volunteer in the facility in any 
capacity whether or not employed by the 
operator. II 
(20) The facility shall develop and offer an 
in-service orientation and continuing educa-
tional program for the development and 
improvement of skills of all the facility’s per-
sonnel, appropriate for their job function. 
Facilities shall begin providing orientation on 
the first day of employment for all personnel 
including licensed nurses and other profes-
sionals. At a minimum, this shall cover pre-
vention and control of infection, facility poli-
cies and procedures including emergency 
protocol, job responsibilities and lines of 
authority, confidentiality of resident informa-
tion, and preservation of resident dignity 
including protection of the resident’s privacy 
and instruction regarding the property rights 
of residents. II/III 
(21) Nursing Assistant Training Program. 
(A) All nursing assistants shall successful-
ly complete the entire basic course (including 
passing the final examination) of the nursing 
assistant training program and be certified 
within four (4) months of employment. II/III 
(B) Nursing assistants who have not suc-
cessfully completed the nursing assistant 
training program prior to employment may 
begin duties as a nursing assistant and may 
provide direct resident care only if under the 
direct supervision of a licensed nurse prior to 
the completion of the seventy-five (75) class-
room hours of the training program. For the 
purpose of this rule, direct supervision shall 
mean close contact whereby the licensed 
nurse is able to respond quickly to the needs 
of the resident. The nursing assistant shall not 
perform any care or services for which he or 
she has not been trained nor found proficient 
by a licensed nurse. II/III 
(C) Prior to any direct resident contact, an 
individual enrolled in the nursing assistant 
training program’s basic course in a Medicare 
or Medicaid certified facility shall complete 
at least a total of sixteen (16) of the required 
seventy-five (75) hours of instructional train-
ing in communication and interpersonal 
skills; infection control; safety/emergency 
procedures, including the Heimlich maneu-
ver; promoting residents’ independence; and 
respecting residents’ rights. II/III 
(22) The facility must ensure there is a sys-
tem of in-service training for nursing person-
nel which identifies training needs related to 
problems, needs, care of residents and infec-
tion control and is sufficient to ensure staff’s 
continuing competency. II/III 
(23) Facilities shall conduct at least annual 
in-service education for nursing personnel 
including training in restorative nursing. This 
training by a registered nurse or qualified 
therapist shall include: turning and position-
ing for the bedridden resident, range of 
motion (ROM) exercises, ambulation assis-
tance, transfer procedures, bowel and bladder 
retraining and self-care activities of daily liv-
ing. II/III 
(24) A registered nurse shall be responsible 
for the planning and then assuring the imple-
mentation of the in-service education pro-
gram for nursing personnel. II 
(25) Facilities shall maintain records which 
indicate the subject of, and attendance at, all 
in-service sessions. III 
(26) All authorized personnel shall have 
access to the legal name of each resident, 
name and telephone number of physician and 
next of kin or responsible party of each resi-
dent to contact in the event of emergency. 
II/III 
(27) The facility must develop and implement 
policies and procedures which ensure 
employees are screened to identify communi-
cable diseases and ensure that employees 
diagnosed with communicable diseases do 
not expose residents to such diseases. The 
facility’s policies and procedures must com-
ply with the Missouri Department of Health’s 
regulations pertaining to communicable dis-
eases, specifically 19 CSR 20-20.010 through 
19 CSR 20-20.100, as amended. II 
(28) The administrator shall maintain on the 
premises an individual personnel record on 
each employee of the facility which shall 
include: the employee’s name and address; 
Social Security number; date of birth; date of 
employment; experience and education; ref-
erences, if available; the result of background 
checks required by section 660.317, RSMo; a 
copy of any good cause waiver, granted by the 
division, if applicable; position in the facili-
ty; record that the employee was instructed 
on resident’s rights; basic orientation 
received; and reason for termination, if appli-
cable. Documentation shall be on file of all 
training received within the facility in addi-
tion to current copies of licenses, transcripts, 
certificates or statements evidencing compe-
tency for the position held. Facilities shall 
retain personnel records for at least one (1) 
year following termination of employment. 
III 
(29) Facilities shall maintain written docu-
mentation on the premises showing actual 
hours worked by each employee. III 
(30) All persons who have or may have con-
tact with residents shall at all times when on 
duty or delivering services wear an identifi-
cation badge. The badge shall give their 
name, title and, if applicable the status of 
their license or certification as any kind of 
health care professional. This rule shall apply 
to all personnel who provide services to any 
resident directly or indirectly. III 
(31) Employees other than nursing personnel 
shall be at least sixteen (16) years of age.II/III 
(32) Nursing personnel shall be at least eigh-
teen (18) years of age except that a person 
between the ages of seventeen (17) years of 
age and eighteen (18) years of age may pro-
vide direct resident care if the individual is 
listed as a certified nursing assistant with an 
active status on the department’s certified 
nursing assistant registry. The individual 
shall work under the direct supervision of a 
licensed nurse and shall never be left respon-
sible for a nursing unit. II/III 
(33) All nurses employed by the facility shall 
be currently licensed in Missouri. II 
(34) All facilities shall employ a director of 
nursing on a full-time basis who shall be 
responsible for the quality of patient care and 
supervision of personnel rendering patient 
care. II 
(35) Licensed Nursing Requirements; Skilled 
Nursing Facility. 
(A) The director of nursing shall be a reg-
istered nurse. II 
(B) A registered nurse shall be on duty in 
the facility on the day shift. Either a licensed 
practical nurse (LPN) or a registered profes-
sional nurse (RN) shall be on duty in the 
facility on both the evening and night shifts. 
II 
(C) A registered nurse shall be on call dur-
ing the time when only an LPN is on duty. II 
(36) Licensed Nursing Requirements; Inter-
mediate Care Facilities. 
(A) The director of nursing shall be either 
an RN or an LPN. II 
(B) When the director of nursing is an 
LPN, an RN shall be employed as consultant 
a minimum of four (4) hours per week to pro-
vide consultation to the administrator and the 
director of nursing in matters relating to nurs-
ing care in the facility. II 
(C) An LPN or RN shall be on duty and in 
the facility on the day shift. II 
(D) An LPN or RN shall be on call twen-
ty-four (24) hours a day, seven (7) days a 
week. I/II 
(37) All facilities shall employ nursing per-
sonnel in sufficient numbers and with suffi-
cient qualifications to provide nursing and 
related services which enable each resident to 
attain or maintain the highest practicable 
level of physical, mental and psychosocial 
well-being. Each facility shall have a licensed 
nurse in charge who is responsible for evalu-
ating the needs of the residents on a daily and 
continuous basis to ensure there are suffi-
cient, trained staff present to meet those 
needs. I/II 
(38) Nursing personnel shall be on duty at all 
times on each resident-occupied floor. II 
(39) Nursing personnel in any facility with 
more than twenty (20) residents shall not rou-
tinely perform non-nursing duties. II/III 
(40) Nursing personnel in facilities with 
twenty (20) residents or less shall perform 
non-nursing duties only if acceptable infec-
tion control measures are maintained. II/III 
(41) Each facility resident shall be under the 
medical supervision of a Missouri-licensed 
physician who has been informed of the facil-
ity’s emergency medical procedures and is 
kept informed of treatments or medications 
prescribed by any other professional lawfully 
authorized to prescribe medications. I/II 
(42) Facilities shall ensure that at the time the 
resident is admitted, the facility obtains from 
a physician the resident’s primary diagnosis 
along with current medical findings and the 
written orders for the immediate care of the 
resident. II/III 
(43) The facility shall ensure that the resi-
dent’s private physician, the physician’s 
designee, the facility’s supervising physician, 
or an alternate physician shall examine the 
resident at least annually, and shall examine 
the resident as often as necessary to ensure 
proper medical care. I/II 
(44) For each medical examination, the physi-
cian must review the resident’s care, includ-
ing medications and treatments; write, sign, 
and date progress notes; and sign and date all 
orders. The facility shall establish a policy 
requiring the physician to sign orders and to 
complete all other documentation required if 
the physician does not visit the resident rou-
tinely. II/III 
18 CODE OF STATE REGULATIONS (11/30/21) JOHN R. ASHCROFT 
Secretary of State
19 CSR 30-85—DEPARTMENT OF HEALTH AND 
 SENIOR SERVICES Division 30—Division of Regulation and Licensure

 CODE OF STATE REGULATIONS 19JOHN R. ASHCROFT (11/30/21) 
Secretary of State
Chapter 85—Intermediate Care and Skilled Nursing Facility 19 CSR 30-85
(45) No medication, treatment, or diet shall 
be given without a written order from a per-
son lawfully authorized to prescribe such and 
the order shall be followed. No restraint shall 
be applied except as provided in 13 CSR 15-
18.010, Resident Rights. I/II 
(46) There shall be a safe and effective sys-
tem of medication distribution, administra-
tion, control, and use. I/II 
(47) V erbal and telephone orders for medica-
tion or treatment shall be given only to those 
individuals licensed or certified to accept 
orders. Orders shall be immediately reduced 
to writing and signed by that individual. If a 
telephone order is given to a certified medi-
cation technician, an initial dose of medica-
tion or treatment shall not be given until the 
order has been reviewed by telephone or in 
person by a licensed nurse or pharmacist. 
The review shall be documented by the 
reviewer co-signing the telephone order. II 
(48) Medications shall be administered only 
by a licensed physician, a licensed nurse, or 
a medication technician who has successfully 
completed the state-approved course for med-
ication administration. II 
(49) Injectable medication, other than 
insulin, shall be administered only by a 
licensed physician or a licensed nurse. Insulin 
injections may be administered by a certified 
medication technician who has successfully 
completed the state-approved course for 
insulin administration. II 
(50) Self-administration of medication is per-
mitted only if approved in writing by the res-
ident’s physician, and it is in accordance with 
the facility’s policy and procedures. II 
(51) All medication errors and adverse reac-
tions shall be reported immediately to the 
nursing supervisor and the resident’s physi-
cian and, if there was a dispensing error, to 
the issuing pharmacist. II/III 
(52) At least monthly a pharmacist or a reg-
istered nurse shall review the drug regimen of 
each resident. Irregularities shall be reported 
in writing to the resident’s physician, the 
administrator, and the director of nurses. 
There must be written documentation which 
indicates how the reports were acted upon. 
II/III 
(53) All prescription medications shall be 
supplied as individual prescriptions. All med-
ications, including over-the-counter medica-
tions, shall be packaged and labeled in accor-
dance with applicable professional pharmacy 
standards and state and federal drug laws and 
regulations. The United States Pharma-
copoeia (USP) labeling shall include accesso-
ry and cautionary instructions as well as the 
expiration date, when applicable, and the 
name of the medication as specified in the 
physician’s order. Over-the-counter medica-
tions for individual residents shall be labeled 
with at least the resident’s name. II/III 
(54) If the resident brings medications to the 
facility, they shall not be used unless the con-
tents have been examined, identified, and 
documented by a pharmacist or a physician. 
II/III 
(55) Facilities shall store all external and 
internal medications at appropriate tempera-
tures in a safe, clean place and in an orderly 
manner apart from foodstuffs and dangerous 
chemicals. A facility shall secure all medica-
tions, including those refrigerated, behind at 
least one (1) locked door or cabinet. Facili-
ties shall store containers of discontinued 
medication separately from current medica-
tions. II/III 
(56) Facilities shall store Schedule II medica-
tions, including those in the emergency drug 
supply, under double lock separately from 
noncontrolled medication. Schedule II medi-
cations may be stored and handled with other 
noncontrolled medication if the facility has a 
single unit dose drug distribution system in 
which the quantity stored is minimal and a 
missing dose can be readily detected. II 
(57) Upon discharge or transfer, a resident 
may be given medications with a written 
order from the physician. Instructions for the 
use of those medications will be provided to 
the resident or the resident’s designee. III 
(58) All non-unit doses and all controlled 
substances which have been discontinued 
must be destroyed on the premises within 
thirty (30) days. Outdated, contaminated, or 
deteriorated medications and non-unit dose 
medications of deceased residents shall be 
destroyed within thirty (30) days. Unit dose 
medications returnable to the pharmacy shall 
be returned within thirty (30) days. II/III 
(59) Medications shall be destroyed in the 
facility by a pharmacist and a licensed nurse 
or by two (2) licensed nurses. III 
(60) Facilities shall maintain records of med-
ication destroyed in the facility. Records shall 
include: the resident’s name; the date; the 
name, strength, and quantity of the medica-
tion; the prescription number; and the signa-
tures of the participating parties. III 
(61) The facility shall maintain records of 
medication released to the family or resident 
upon discharge or to the pharmacy. Records 
shall include: the resident’s name; the date; 
the name, strength, and quantity of the med-
ication; the prescription number; and the sig-
nature of the persons releasing and receiving 
the medication. III 
(62) The facility must establish a system of 
records of receipt and disposition of all con-
trolled drugs in sufficient detail to enable an 
accurate reconciliation. The system must 
enable the facility to determine that drug 
records are in order and that an account of all 
controlled drugs is maintained and recon-
ciled. II/III 
(63) Facilities shall make available to all 
nursing staff up-to-date reference material on 
all medications in use in the facility. III 
(64) The facility shall develop policies to 
identify any emergency stock supply of pre-
scription medications to be kept in the facility 
for resident use only. This emergency drug 
supply must be checked at least monthly by a 
pharmacist to ensure its safety for use and 
compliance with facility policy. A facility 
shall have the emergency drug supply readily 
available to medical personnel and use of 
medications in the emergency drug supply 
shall assure accountability. III 
(65) Each resident shall receive twenty-four- 
(24-) hour protective oversight and supervi-
sion. For residents departing the premises on 
voluntary leave, the facility shall have, at a 
minimum, a procedure to inquire of the resi-
dent or resident’s guardian of the resident’s 
departure, of the resident’s estimated length 
of absence from the facility, and of the resi-
dent’s whereabouts while on voluntary leave. 
I/II 
(66) Each resident shall receive personal 
attention and nursing care in accordance with 
his/her condition and consistent with current 
acceptable nursing practice. I/II 
(67) Each resident shall be clean, dry, and 
free of body and mouth odor that is offensive 
to others. I/II 
(68) Taking into consideration the resident’s 
preferences, residents shall be well-groomed 
and dressed appropriately for the time of day, 
the environment and any identified medical 
conditions. II/III 
20 CODE OF STATE REGULATIONS (11/30/21) JOHN R. ASHCROFT 
Secretary of State
19 CSR 30-85—DEPARTMENT OF HEALTH AND 
 SENIOR SERVICES Division 30—Division of Regulation and Licensure
(69) Residents who are physically or mentally 
incapable, or both, of changing their own 
positions shall have their positions changed at 
least every two (2) hours and shall be provid-
ed supportive devices to maintain good body 
alignment. I/II 
(70) The facility must provide each resident 
the opportunity to access sufficient fluids to 
maintain proper hydration in accordance with 
the resident’s medical condition and goals of 
treatment as documented in the medical 
record. I/II 
(71) All residents who require assistance at 
mealtimes, whether it be preparation of the 
food items or actual feeding, shall be provid-
ed the assistance upon delivery of the tray. 
Facilities shall provide dining room supervi-
sion during meals. II/III 
(72) Facilities shall provide each resident, 
according to his/her needs, with restorative 
nursing to encou rage independence, activity 
and self-help to maintain strength and mobil-
ity. Each resident shall be out of bed as 
desired unless medically contraindicated. II 
(73) Each resident shall have skin care 
including the application of oil, lotion, and 
cream as needed to prevent dryness and scal-
ing of skin. II/III 
(74) Facilities shall keep residents free from 
avoidable pressure sores, taking measures 
toward prevention. If sores exist, staff shall 
give adequate treatment. I/II 
(75) Facility staff shall check residents 
requiring restraints every thirty (30) minutes 
and exercise the residents every two (2) 
hours. II/III 
(76) Facilities shall not use locked restraints. 
I 
(77) Residents shall be cared for by using 
acceptable infection control procedures to 
prevent the spread of infection. The facility 
shall make a report to the division within 
seven (7) days if a resident is diagnosed as 
having a communicable disease, as deter-
mined by the Missouri Department of Health 
and listed in the Code of State Regulations 
pertaining to communicable diseases, specif-
ically 19 CSR 20-20.020, as amended. I/II 
(78) In the event of accident, injury, or signif-
icant change in the resident’s condition, facil-
ity staff shall notify the resident’s physician 
in accordance with the facility’s emergency 
treatment policies which have been approved 
by the supervising physician. I/II 
(79) In the event of accident, injury, or signif-
icant change in the resident’s conditions, 
facility staff shall immediately notify the per-
son designated in the resident’s record as the 
designee or responsible party. III 
(80) Staff shall inform the administrator of 
accidents, injuries, and unusual occurrences 
which adversely affect, or could adversely 
affect, the resident. The facility shall develop 
and implement responsive plans of action. III 
(81) Facilities shall ensure that each resident 
is provided individual personal care items 
necessary for good grooming. Items shall be 
stored and maintained in a clean manner 
within the resident’s room. III 
(82) Facilities shall provide equipment and 
nursing supplies in sufficient number to meet 
the needs of the residents. II/III 
(83) Facilities shall keep all utensils and 
equipment in good condition, effectively san-
itized, sterilized, or both, and stored to pre-
vent contamination. II/III 
(84) Staff shall ensure that bedpans, com-
modes, and urinals are covered after use, 
emptied promptly, and thoroughly cleaned 
after use. II/III 
(85) Facilities shall provide and use a suffi-
cient supply of clean bed linen, including 
sheets, pillow cases, blankets, and mattress 
pads to assure that resident beds are kept 
clean, neat, dry, and odor free. II/III 
(86) Staff shall use moisture proof covers as 
necessary to keep mattresses and pillows 
clean, dry, and odor free. II/III 
(87) Facilities shall provide each resident 
with fresh bath towels, hand towels, and 
washcloths as needed for individual usage. 
II/III 
(88) In addition to rehabilitative or restorative 
nursing, all facilities shall provide or make 
arrangements for providing rehabilitation ser-
vices to all residents according to their needs. 
If a resident needs rehabilitation services, a 
qualified therapist shall perform an evaluation 
on written order of the resident’s physician. 
II/III 
(89) Facilities shall ensure that rehabilitation 
services are provided by or under the on-site 
supervision of a qualified therapist or a qual-
ified therapy assistant who works under the 
general supervision of a qualified therapist. 
I/II 
(90) Staff shall include the following in doc-
umentation of rehabilitation services: physi-
cian’s written approval for proposed plan of 
care; progress notes at least every thirty (30) 
days by the therapist; daily record of the pro-
cedure(s) performed; summary of therapy 
when rehabilitation has been reached and, if 
applicable, recommendations for mainte-
nance procedures by restorative nursing. III 
(91) The facility shall designate a staff mem-
ber to be responsible for the facility’s social 
services program. The designated staff per-
son shall be capable of identifying social and 
emotional needs, knowledgeable of methods 
or resources, or a combination of these to use 
to meet them and services shall be provided 
to residents as needed. II/III 
(92) The facility shall designate an employee 
to be responsible for the activity program. 
The designated person shall be capable of 
identifying activity needs of residents, 
designing and implementing programs to 
maintain or increase, or both, the resident’s 
capability in activities of daily living. Facili-
ties shall provide activity programs on a reg-
ular basis. Each resident shall have a planned 
activity program which includes individual-
ized activities, group activities, and activities 
outside the facility as appropriate to his/her 
needs and interests. II/III 
(93) The facility shall provide and use ade-
quate space and equipment within the facility 
for the identified activity needs of residents. 
II/III 
(94) The facility shall establish and maintain 
a program for informing all residents in 
advance of available activities, activity loca-
tion and time. III 
(95) Facility staff shall include the following 
general information in admission records: 
resident’s name; prior address; age (birth 
date); sex; marital status; Social Security 
number; Medicare and Medicaid numbers; 
date of admission; name, address, and tele-
phone number of responsible party; name, 
address, and telephone number of attending 
physician; height and weight on admission; 
inventory of resident’s personal possessions 
upon admission; and names of preferred den-
tist, pharmacist, and funeral director. II/III 
(96) Facility staff shall include physician 
entries in the medical record with the following 
information: admission diagnosis,
 admission 
 CODE OF STATE REGULATIONS 21JOHN R. ASHCROFT (11/30/21) 
Secretary of State
Chapter 85—Intermediate Care and Skilled Nursing Facility 19 CSR 30-85
physical and findings of subsequent examina-
tions; progress notes; orders for all medica-
tions and treatment; orders for extent of 
activity; orders for restraints including type 
and reason for restraint; orders for diet; and 
discharge diagnosis or cause of death. II/III 
(97) Residents admitted to a facility on refer-
ral by the Department of Mental Health shall 
have an individualized treatment plan or indi-
vidualized habilitation plan on file which is 
updated annually. III 
(98) Facilities shall ensure that the clinical 
record contains sufficient information to— 
(A) Identify the resident; 
(B) Reflect the initial and ongoing assess-
ments and interventions by each discipline 
involved in the care and treatment of the res-
ident; and 
(C) Identify the discharge or transfer desti-
nation. II/III 
(99) Facilities shall ensure that the resident’s 
clinical record must contain progress notes 
that include, but are not limited to: 
(A) Response to care and treatment; 
(B) Change(s) in physical, mental, and 
psychosocial condition; 
(C) Reasons for changes in treatment; and 
(D) Reasons for transfer or discharge. 
II/III 
(100) The facility must safeguard clinical 
record information against loss, destruction, 
or unauthorized use. III 
(101) The facility must keep all information 
confidential that is contained in the resident’s 
records regardless of the form or sto rage 
method of the records, including video-, 
audio-, or computer-stored information. III 
(102) The facility must maintain clinical 
records on each resident in accordance with 
accepted professional standards and prac-
tices. These records shall be complete, accu-
rately documented, readily accessible on 
each nursing unit, and systematically orga-
nized. II/III 
(103) Facilities must retain clinical records 
for the period of time required by state law or 
five (5) years from the date of discharge when 
there is no requirement in state law. III 
(104) Facilities shall retain all financial 
records related to the facility operation for 
seven (7) years from the end of the facility’s 
fiscal year. III 
(105) In the event the resident is transferred 
from the facility, the resident shall be accom-
panied by a copy of the medical history, 
transfer forms which include the physical 
exam report, nursing summary, and report of 
orders physicians prescribed. II/III 
AUTHORITY: sections 198.006, 198.009, 
198.079, RSMo 2016.* This rule originally 
filed as 13 CSR 15-14.042. Original rule 
filed July 13, 1983, effective Oct. 13, 1983. 
Emergency amendment filed Nov. 9, 1983, 
effective Nov. 19, 1983, expired March 18, 
1984. Amended: Filed Nov. 9, 1983, effective 
Feb. 1 1, 1984. Amended: Filed Sept. 12, 
1984, effective Dec. 13, 1984. Amended: 
Filed Aug. 1, 1988, effective Nov. 10, 1988. 
Amended: Filed Jan. 3, 1992, effective Aug. 
6, 1992. Amended: Feb. 13, 1998, effective 
Sept. 30, 1998. Amended: Filed Feb. 15, 
2000, effective Aug. 30, 2000. Moved to 19 
CSR 30-85.042, effective Aug. 28, 2001. 
Emergency amendment filed Sept. 12, 2003, 
effective Sept. 22, 2003, expired March 19, 
2004. Amended: Filed Sept. 12, 2003, effec-
tive Feb. 29, 2004. ** Amended: Filed June 
14, 2021, effective Dec. 30, 2021. 
*Original authority: 198.006, RSMo 1979, amended 
1984, 1987, 2003; 198.009, RSMo 2016; and 198.079, 
RSMo 1979. 
**Pursuant to Executive Order 21-07, 19 CSR 30-85.042, sections 
(7) and (21) was suspended from April 16, 2020 through May 1, 
2021 and section (27) was suspended from April 23, 2020 through 
August 31, 2021. Pursuant to Executive Order 21-09, 19 CSR 30-
85.042, sections (1 1), (20), (33), (40), (49), and (50) was suspended 
from April 15, 2020 through December 31, 2021 and sections (9) 
and (1 1), subsection (35)(B), section (39), and section 198.082, 
RSMo was suspended from April 16, 2020 through December 31, 
2021. 

19 CSR 30-85.052 Dietary Requirements 
for New and Existing Intermediate Care 
and Skilled Nursing Facilities 
PURPOSE: This rule establishes dietary 
requirements for new and existing intermedi-
ate care and skilled nursing facilities. 
Editor’s Note: All rules relating to long-term 
care facilities licensed by the Division of 
Aging are followed by a Roman Numeral 
notation which refers to the class (either 
Class I, II or III) of standard as designated in 
section 198.085.1, RSMo. 
(1) Each resident shall be served nutritious 
food, properly prepared and appropriately 
seasoned, taking into consideration resident 
food preferences, to provide an adequate diet 
in accordance with the physician’s order and 
as recommended by the National Research 
Council. Nutritional needs of residents shall 
be met and shall be based on the individual’s 
circumstances, medical condition and goals 
of treatment as determined and justified by 
the physician. A qualified professional, such 
as a dietitian or registered nurse, shall regu-
larly assess these needs and shall keep the 
physician informed of the nutritional status of 
the resident. I/II 
(2) At least three (3) substantial meals or 
other equivalent shall be served daily at reg-
ular hours with supplementary feedings as 
necessary. At least two (2) meals shall be 
hot.II/III 
(3) Foods shall be prepared and served using 
methods that conserve nutritive value, flavor 
and appearance. II/III 
(4) Special attention shall be given to the tex-
ture of food given to residents who have 
chewing difficulty. II/III 
(5) Provision shall be made to assure that hot 
food is served hot and cold food is served 
cold. II 
(6) If a resident refuses food served, appro-
priate substitutes of similar nutritive value 
shall be offered. II/III 
(7) Bedtime snacks of nourishing quality shall 
be offered to all residents unless medically 
contraindicated. III 
(8) Tray service and dining room service for 
residents shall be attractive and each resident 
shall receive appropriate table service. III 
(9) Each resident who is served meals in bed 
or in a chair not within the dining area shall 
be provided with either a table, an overbed 
table or an overbed tray of sturdy construc-
tion which is positioned so that the resident 
can eat comfortably. III 
(10) A time schedule for service of meals to 
residents shall be established. Meals shall be 
served approximately four to five (4–5) hours 
apart and not longer than fourteen (14) hours 
from a substantial evening meal to breakfast. 
II/III 
(11) A minimum of thirty (30) minutes shall 
be given for eating meals. Residents who eat 
slowly or who need assistance shall be given 
as much time to eat as necessary. II/III 
(12) An identification system shall be estab-
lished to assure that each resident receives the 
diet as ordered. II/III 
(13) If the residents have objectionable table 
manners, an alternate method of meal service 
22 CODE OF STATE REGULATIONS (11/30/21) JOHN R. ASHCROFT 
Secretary of State
19 CSR 30-85—DEPARTMENT OF HEALTH AND 
 SENIOR SERVICES Division 30—Division of Regulation and Licensure
shall be provided. III 
(14) There shall be sufficient personnel prop-
erly trained in their duties to assure adequate 
preparation and serving of food. II 
(15) All facilities shall employ a food service 
supervisor who shall have overall supervisory 
responsibility for dietary services. II 
(16) Menus for special prescribed diets shall 
be reviewed and approved in writing by either 
a qualified dietitian, a registered nurse or a 
physician. II/III 
(17) If food preparation, service, or both, 
within the facility is handled through a con-
tractual arrangement, all regulations govern-
ing sanitation (13 CSR 15-17), dietary ser-
vice and contractual personnel shall be met 
and maintained. II/III 
(18) If it is determined by the Division of 
Aging that due to the complexity of pre-
scribed diets or that the food service supervi-
sor is unable to assure compliance with the 
dietary requirements, the facility shall be 
required to employ, for specified periods of 
time, a qualified dietitian to serve as a con-
sultant and until the food service management 
improves to assure that the residents’ needs 
are being met. II 
(19) A current record of purchased food shall 
be kept to show the kind and amount of food 
purchased each month. III 
(20) Supplies of staple food for a minimum of 
a one (1)-week period and of perishable foods 
for a minimum of a three (3)-day period shall 
be maintained on the premises. II 
(21) Menus for all diets shall be planned at 
least two (2) weeks in advance. If cycle 
menus are used, the cycle must cover a mini-
mum of three (3) weeks and must be different 
each day of the week. Menus showing the 
foods and amounts of food to be served each 
day during the current week shall be posted 
where seen readily as food is prepared and 
served. Each day’s menu shall show the date 
it was actually used and shall be kept on file 
for thirty (30) days. A list of substitutions 
shall be kept for thirty (30) days. III 
(22) A file of standardized recipes shall be 
used. III 
(23) A diet manual approved by the Division 
of Aging shall be readily available to attend-
ing physicians, nursing and dietary person-
nel. III 
AUTHORITY: section 198.009, RSMo 1986.* 
This rule originally filed as 13 CSR 15-
14.052. Original rule filed July 13, 1983, 
effective Oct. 13, 1983. Amended: Filed Aug. 
1, 1988, effective Nov. 10, 1988. Amended: 
Filed Jan. 3, 1992, effective Aug. 6, 1992. 
Moved to 19 CSR 30-85.052, effective Aug. 
28, 2001. ** 
*Original authority: 198.009, RSMo 1979. 
**Pursuant to Executive Order 21-09, 19 CSR 30-85.052, sections 
(14), (16), and (21) was suspended from April 15, 2020 through 
December 31, 2021.