K-Tag K927 active

Gas Equipment – Transfilling Cylinders

Jurisdiction: CM Agency: Centers for Medicare & Medicaid Services
SNF (100%)
Plain-English summary

This regulation governs the safe transfilling of oxygen and other gases between cylinders in healthcare facilities, requiring compliance with CGA P-2.5 standards and NFPA 99 provisions. It prohibits transfilling in patient care rooms and sets specific conditions for transfilling to liquid oxygen containers or portable containers based on pressure thresholds. Facility operators must ensure all gas transfilling activities meet the referenced CGA and NFPA 99 standards.

View official source
Regulation text
K927 Gas Equipment – Transfilling Cylinders 
Transfilling of oxygen from one cylinder to another is in accordance with 
CGA P-2.5, Transfilling of High Pressure Gaseous Oxygen Used for 
Respiration. Transfilling of any gas from one cylinder to another is 
prohibited in patient care rooms. Transfilling to liquid oxygen containers or 
to portable containers over 50 psi comply with conditions under 11.5.2.3.1 
(NFPA 99). Transfilling to liquid oxygen containers or to port able containers 
under 50 psi comply with conditions under 11.5.2.3.2 (NFPA 99). 
11.5.2.2 (NFPA 99) 
Form CMS-2786R (07/2018) Page 46 

Name of Facility 2012 LIFE SAFETY CODE
ID 
PREFIX MET NOT 
MET N/A REMARKS