Electrical Systems – Essential Electric System Maintenance and

Jurisdiction: CM Agency: Centers for Medicare & Medicaid Services
SNF (100%)
Plain-English summary

This regulation establishes requirements for the maintenance and testing of emergency electrical systems (EES), including generators and alternate power sources, transfer switches, circuit breakers, and stored energy systems. Facilities must ensure the generator can supply power within 10 seconds, conduct weekly inspections, monthly and periodic load tests, and a 4-hour test every 36 months. Written records must be maintained, and EES panels and circuits must be clearly marked and separated from normal power circuits.

View official source
Regulation text
K918 Electrical Systems – Essential Electric System Maintenance and 
Testing 
The generator or other alternate power source and associated equipment is 
capable of supplying service within 10 seconds. If the 10-second criterion is 
not met during the monthly test, a process shall be provided to annually 
confirm this capability for the life safety and critical branches. Maintenance 
and testing of the generator and transfer switches are performed in 
accordance with NFPA 110. 
Generator sets are inspected weekly, exercised under load 30 minutes 12 
times a year in 20-40 day intervals, and exercised once every 36 months for 
4 continuous hours. Scheduled test under load conditions include a 
complete simulated cold start and automatic or manual transfer of all EES 
loads, and are conducted by competent personnel. Maintenance and 
testing of stored energy power sources (Type 3 EES) are in accordance 
with NFPA 111. Main and feeder circuit breakers are inspected annually, 
and a program for periodically exercising the components is established 
according to manufacturer requirements. Written records of maintenance 
and testing are maintained and readily available. EES electrical panels and 
circuits are marked, readily identifiable, and separate from normal power 
circuits. Minimizing the possibility of damage of the emergency power 
source is a design consideration for new installations. 
6.4.4, 6.5.4, 6.6.4 (NFPA 99), NFPA 110, NFPA 111, 700.10 (NFPA 70) 