K-Tag K916 active

Electrical Systems – Essential Electric System Alarm Annunciator

Jurisdiction: CM Agency: Centers for Medicare & Medicaid Services
PSYCH_FACILITY (40%) SNF (100%)
Plain-English summary

Facilities must install a remote, battery-powered alarm annunciator located outside the generator room in a position readily observable by operating personnel. The annunciator must be hard-wired to indicate alarm conditions of the emergency power source and cannot be replaced by a centralized computer or building information system. This requirement references NFPA 99 standards for essential electrical systems.

View official source
Regulation text
K916 Electrical Systems – Essential Electric System Alarm Annunciator 
A remote annunciator that is storage battery powered is provided to operate 
outside of the generating room in a location readily observed by operating 
personnel. The annunciator is hard-wired to indicate alarm conditions of 
the emergency power source. A centralized computer system (e.g., 
building information system) is not to be substituted for the alarm 
annunciator. 
6.4.1.1.17, 6.4.1.1.17.5 (NFPA 99)