Regulation detail

K-Tag K915

Up to date
Ask Ariadne
SR
K-Tag K915 active

Electrical Systems – Essential Electric System Categories

Jurisdiction: CM Agency: Centers for Medicare & Medicaid Services
SNF (100%)
Plain-English summary

This regulation specifies electrical system requirements for patient care rooms in healthcare facilities, categorizing rooms by risk level (Category 1 critical care, Category 2 general care, Category 3 basic care) and mandating corresponding Essential Electrical System (EES) types. Facilities must ensure critical care rooms with life support equipment are served by a Type 1 EES, general care rooms by Type 1 or Type 2 EES, and that Type 3 EES life safety branches provide at least 1.5 hours of alternate power. This is a CMS Life Safety Code survey tag (Form CMS-2786R) governing physical plant electrical infrastructure standards.

View official source
Regulation text
K915 Electrical Systems – Essential Electric System Categories 
☐ Critical care rooms (Category 1) in which electrical system failure is likely
to cause major injury or death of patients, including all rooms where electric
life support equipment is required, are served by a Type 1 EES.
☐ General care rooms (Category 2) in which electrical system failure is
likely to cause minor injury to patients (Category 2) are served by a Type 1
or Type 2 EES.
☐ Basic care rooms (Category 3) in which electrical system failure is not
likely to cause injury to patients and rooms other than patient care rooms
are not required to be served by an EES. Type 3 EES life safety branch has
an alternate source of power that will be effective for 1 1/2 hours.
3.3.138, 6.3.2.2.10, 6.6.2.2.2, 6.6.3.1.1 (NFPA 99), TIA 12-3 
Form CMS-2786R (07/2018) Page 41 

Name of Facility 2012 LIFE SAFETY CODE
ID 
PREFIX MET NOT 
MET N/A REMARKS