Regulation detail

K-Tag K913

Up to date
Ask Ariadne
SR
K-Tag K913 active

Electrical Systems – Wet Procedure Locations

Jurisdiction: CM Agency: Centers for Medicare & Medicaid Services
SNF (100%)
Plain-English summary

Facilities must classify operating rooms as wet procedure locations unless a governing body risk assessment determines otherwise. Operating rooms designated as wet locations must be protected by isolated power systems or ground-fault circuit interrupters. A written record of any risk assessment must be maintained and made available for inspection.

View official source
Regulation text
K913 Electrical Systems – Wet Procedure Locations 
Operating rooms are considered wet procedure locations, unless otherwise 
determined by a risk assessment conducted by the facility governing body. 
Operating rooms defined as wet locations are protected by either isolated 
power or ground-fault circuit interrupters. A written record of the risk 
assessment is maintained and available for inspection. 
6.3.2.2.8.4, 6.3.2.2.8.7, 6.4.4.2