K-Tag K910 active

Gas and Vacuum Piped Systems – Modifications

Jurisdiction: CM Agency: Centers for Medicare & Medicaid Services
SNF (100%)
Plain-English summary

This regulation requires that whenever modifications breach a medical gas or vacuum pipeline, all necessary installer and verification tests specified under NFPA 99 must be conducted on the downstream portion of the affected system. Permanent records of all required system verification tests must be maintained. This is a facility infrastructure/safety standard applicable to settings that use piped medical gas and vacuum systems.

View official source
Regulation text
K910 Gas and Vacuum Piped Systems – Modifications 
Whenever modifications are made that breach the pipeline, any necessary 
installer and verification test specified in 5.1.2 is conducted on the 
downstream portion of the medical gas piping system. Permanent records 
of all tests required by system verification tests are maintained. 
5.1.14.4.1, 5.1.14.4.6, 5.2.13, 5.3.13.4.3 (NFPA 99)