Regulation detail

K-Tag K522

Up to date
Ask Ariadne
SR
K-Tag K522 active

18.5.2.2, 19.5.2.2

Jurisdiction: CM Agency: Centers for Medicare & Medicaid Services
PRTF (60%) PSYCH_FACILITY (60%) SNF (100%)
Plain-English summary

This regulation specifies life safety requirements for heating devices (other than central heating plants) in licensed facilities, requiring that combustible materials cannot be ignited by the device, that a safety shutoff feature is present for excessive temperature or ignition failure, and that fuel-fired devices are chimney/vent connected, draw combustion air from outside, and maintain a combustion system separate from occupied areas. This is a CMS Life Safety Code (2012 LSC) physical plant/environment of care standard applied during facility surveys.

View official source
Regulation text
K522
18.5.2.2, 19.5.2.2 
HVAC – Any Heating Device 
Any heating device, other than a central heating plant, is designed and 
installed so combustible materials cannot be ignited by device, and has a 
safety feature to stop fuel and shut down equipment if there is excessive 
temperature or ignition failure. If fuel fired, the device also: 
 is chimney or vent connected.
 takes air for combustion from outside.
 provides for a combustion system separate from occupied area
atmosphere.
Form CMS-2786R (07/2018) 

Name of Facility 2012 LIFE SAFETY CODE
ID 
PREFIX MET NOT 
MET N/A REMARKS