This regulation specifies construction and hardware requirements for doors installed in smoke barriers within existing psychiatric residential treatment facilities (PRTFs), as part of CMS Life Safety Code survey requirements. Operators must ensure smoke barrier doors are at least 1¾-inch thick solid bonded wood-core (or 20-minute fire-resistive construction), are self-closing or automatic-closing, and provide a minimum 32-inch clear opening width. Fixed fire window assemblies and nonrated protective plates of unlimited height are permitted under specified conditions.
View official sourceK374 Subdivision of Building Spaces – Smoke Barrier Doors 2012 EXISTING Doors in smoke barriers are 1¾-inch thick solid bonded wood-core doors or of construction that resists fire for 20 minutes. Nonrated protective plates of unlimited height are permitted. Doors are permitted to have fixed fire window assemblies per 8.5. Doors are self-closing or automatic-closing, do not require latching, and are not required to swing in the direction of egress travel. Door opening provides a minimum clear width of 32 in for swinging or horizontal doors. 19.3.7.6, 19.3.7.8, 19.3.7.9 Form CMS-2786R (07/2018) Page 28 Name of Facility 2012 LIFE SAFETY CODE ID PREFIX MET NOT MET N/A REMARKS