Subdivision of Building Spaces – Smoke Barrier Construction

Jurisdiction: CM Agency: Centers for Medicare & Medicaid Services
PSYCH_FACILITY (60%) SNF (100%)
Plain-English summary

This regulation specifies fire and life safety construction requirements for smoke barriers within building spaces, requiring either a ½-hour (existing buildings) or 1-hour (new buildings) fire resistance rating, with specific provisions for smoke dampers in fully ducted HVAC systems with sprinkler coverage. Facility operators must ensure smoke barriers are constructed per NFPA Life Safety Code standards and document any mechanical smoke control systems in remarks. This is a physical plant/life safety standard applicable to the facility type governed by the broader licensing chapter.

View official source
Regulation text
K372 Subdivision of Building Spaces – Smoke Barrier Construction 
2012 EXISTING 
Smoke barriers shall be constructed to a ½ hour fire resistance rating per 
8.5. Smoke barriers shall be permitted to terminate at an atrium wall. 
Smoke dampers are not required in duct penetrations in fully ducted HVAC 
systems where an approved sprinkler system is installed for smoke 
compartments adjacent to the smoke barrier. 
19.3.7.3, 8.6.7.1(1) 
Describe any mechanical smoke control system in REMARKS. 
2012 NEW 
Smoke barriers shall be constructed to provide at least a 1-hour fire 
resistance rating and constructed in accordance with 8.5. Smoke barriers 
shall be permitted to terminate at an atrium wall. Smoke dampers are not 
required in duct penetrations of fully ducted HVAC systems. 
18.3.7.3, 18.3.7.4, 18.3.7.5, 8.3 
Describe any mechanical smoke control system in REMARKS.