Sprinkler System – Installation

Jurisdiction: CM Agency: Centers for Medicare & Medicaid Services
SNF (100%)
Plain-English summary

This regulation establishes fire sprinkler system installation requirements for nursing homes and hospitals, mandating full building protection via NFPA 13-compliant automatic sprinkler systems. It addresses both existing and new construction, permits alternative protection measures in Type I and II construction where sprinklers are prohibited by state or local law, and specifies limited exemptions for small patient room clothes closets in hospitals. Facility operators must ensure sprinkler systems meet the referenced NFPA 13 standards and applicable Life Safety Code sections.

View official source
Regulation text
K351 Sprinkler System – Installation 
2012 EXISTING 
Nursing homes, and hospitals where required by construction type, are 
protected throughout by an approved automatic sprinkler system in 
accordance with NFPA 13, Standard for the Installation of Sprinkler 
Systems. 
In Type I and II construction, alternative protection measures are permitted 
to be substituted for sprinkler protection in specific areas where state or 
local regulations prohibit sprinklers. 
In hospitals, sprinklers are not required in clothes closets of patient sleeping 
rooms where the area of the closet does not exceed 6 ft² and sprinkler 
coverage covers the closet footprint as required by NFPA 13, Standard for 
Installation of Sprinkler Systems. 
19.3.5.1, 19.3.5.2, 19.3.5.3, 19.3.5.4, 19.3.5.5, 19.4.2, 19.3.5.10, 9.7, 
9.7.1.1(1) 
2012 NEW 
Buildings are to be protected throughout by an approved automatic 
sprinkler system in accordance with NFPA 13, Standard for the Installation 
of Sprinkler Systems. 
In Type I and II construction, alternative protection measures are permitted 
to be substituted for sprinkler protection in specific areas where State and 
local regulations prohibit sprinklers. 
Listed quick-response or listed residential sprinklers are used throughout 
smoke compartments with patient sleeping rooms. 
In hospitals, sprinklers are not required in clothes closets of patient sleeping 
rooms where the area of the closet does not exceed 6 ft² and sprinkler 
coverage covers the closet footprint as required by NFPA 13, Standard for 
Installation of Sprinkler Systems. 
18.3.5.1, 18.3.5.4, 18.3.5.5, 18.3.5.6, 9.7, 9.7.1.1(1), 18.3.5.10