This regulation specifies fire and life safety requirements for smoke detection systems in nursing homes, including automatic smoke detection in corridors of smoke compartments containing resident sleeping rooms, with specific exceptions and requirements for electrical interconnection to the fire alarm system. It is a CMS Life Safety Code survey tag (K347) applicable to nursing facility physical plant standards. Facility operators must ensure smoke detectors are installed per the 2012 Life Safety Code (NFPA 101) sections 18/19.3.4.5 and electrically interconnected to the fire alarm system.
View official sourceK347 Smoke Detection 2012 EXISTING Smoke detection systems are provided in spaces open to corridors as required by 19.3.6.1. 19.3.4.5.2 2012 NEW Smoke detection systems are provided in spaces open to corridors as required by 18.3.6.1 In nursing homes, an automatic smoke detection system is installed in the corridors of all smoke compartments containing resident sleeping rooms, unless the resident sleeping rooms have: smoke detection, or automatic door closing devices with integral smoke detectors on the room side that provide occupant notification. Such detectors are electrically interconnected to the fire alarm system. 18.3.4.5.2, 18.3.4.5.3 Form CMS-2786R (07/2018) Page 22 Name of Facility 2012 LIFE SAFETY CODE ID PREFIX MET NOT MET N/A REMARKS