Fire Alarm – Out of Service

Jurisdiction: CM Agency: Centers for Medicare & Medicaid Services
SNF (100%)
Plain-English summary

When a required fire alarm system is out of service for more than 4 hours within a 24-hour period, the facility must notify the authority having jurisdiction and either evacuate the building or implement an approved fire watch for all unprotected occupants until the system is restored. This is a life-safety/fire protection requirement applicable to any facility subject to fire alarm system requirements.

View official source
Regulation text
K346 Fire Alarm – Out of Service 
Where required fire alarm system is out of services for more than 4 hours in 
a 24 hour period, the authority having jurisdiction shall be notified, and the 
building shall be evacuated or an approved fire watch shall be provided for 
all parties left unprotected by the shutdown until the fire alarm system has 
been returned to service. 
9.6.1.6