K-Tag K342 active

Fire Alarm System – Initiation

Jurisdiction: CM Agency: Centers for Medicare & Medicaid Services
PSYCH_FACILITY (60%) SNF (100%)
Plain-English summary

This regulation specifies requirements for fire alarm system initiation in healthcare facilities, requiring manual alarm boxes along egress paths near exits. In patient sleeping areas, alarm boxes at exits may be omitted if boxes are located at all nurse's stations or continuously attended staff locations, remain visible and accessible, and do not exceed 200 feet travel distance. The rule references NFPA Life Safety Code sections governing both new and existing healthcare occupancies.

View official source
Regulation text
K342 Fire Alarm System – Initiation 
Initiation of the fire alarm system is by manual means and by any required 
sprinkler system alarm, detection device, or detection system. Manual 
alarm boxes are provided in the path of egress near each required exit. 
Manual alarm boxes in patient sleeping areas shall not be required at exits 
if manual alarm boxes are located at all nurse’s stations or other 
continuously attended staff location, provided alarm boxes are visible, 
continuously accessible, and 200’ travel distance is not exceeded. 
18.3.4.2.1, 18.3.4.2.2, 19.3.4.2.1, 19.3.4.2.2, 9.6.2.5