Regulation detail

K-Tag K292

Up to date
Ask Ariadne
SR
K-Tag K292 active

Travel Distance to Exits

Jurisdiction: CM Agency: Centers for Medicare & Medicaid Services
PRTF (60%) PSYCH_FACILITY (80%) SNF (100%)
Plain-English summary

This regulation establishes fire and life safety requirements for means of egress in psychiatric facilities, covering travel distances to exits, exit discharge surfaces, illumination of egress paths, emergency lighting duration, and life safety branch electrical requirements for buildings with life support systems. Facility operators must ensure exit travel distances comply with NFPA Life Safety Code limits (150/200 feet), maintain hard-packed all-weather exit discharge surfaces free of obstructions, provide continuously operational or automatic egress illumination, and supply at least 1.5 hours of emergency lighting. These are CMS survey requirements applied via Form CMS-2786R under the 2012 Life Safety Code.

View official source
Regulation text
K292
Travel Distance to Exits 
Travel distance (excluding suites) to exits are measured in accordance with 
7.6. 
 From any point in the room or suite to exit less than or equal to 150
feet (less than or equal to 200 feet if the building is fully
sprinklered).
 Point in a room to room door less than or equal to 50 feet.
 18.2.6, 19.2.6 
Discharge from Exits 
Exit discharge is arranged in accordance with 7.7, provides a level walking 
surface meeting the provisions of 7.1.7 with respect to changes in elevation 
and shall be maintained free of obstructions. Additionally, the exit 
discharge shall be a hard packed all-weather travel surface. 
18.2.7, 19.2.7
 
Illumination of Means of Egress 
Illumination of means of egress, including exit discharge, is arranged in 
accordance with 7.8 and shall be either continuously in operation or 
 capable of automatic operation without manual intervention. 
 18.2.8, 19.2.8 
 Emergency Lighting 
Emergency lighting of at least 1-1/2 hour duration is provided automatically 
in accordance with 7.9. 
18.2.9.1, 19.2.9.1 
 Life Support Means of Egress 
2012 NEW (INDICATE N/A FOR EXISTING) 
Buildings equipped with or requiring the use of life support systems (electro-
 mechanical or inhalation anesthetics) have illumination of means of egress, 
emergency lighting equipment, exit, and directional signs supplied by the 
 life safety branch of the electrical system described in NFPA 99. 
 (Indicate N/A if life support equipment is for emergency purposes only.) 
18.2.9.2, 18.2.10.5 
 MET NOT 
MET N/A REMARKS 
Name of Facility 2012 LIFE SAFETY CODE
 
Form CMS-2786R (07/2018) Page 13 

Name of Facility 2012 LIFE SAFETY CODE
ID 
PREFIX MET NOT 
MET N/A REMARKS