Regulation detail

K-Tag K241

Up to date
Ask Ariadne
SR
K-Tag K241 active

2012 NEW

Jurisdiction: CM Agency: Centers for Medicare & Medicaid Services
PSYCH_FACILITY (100%) SNF (100%)
Plain-English summary

This regulation establishes Life Safety Code requirements for exit access and exit door dimensions in healthcare facilities, specifying minimum clear widths for different facility types and door configurations. Psychiatric hospitals and limited care facilities have a lower minimum door width requirement (32 inches) compared to the general standard (41.5 inches). The regulation also mandates at least two remote exits accessible from every part of every story, with each smoke compartment requiring two distinct egress paths. Facility operators must ensure door hardware, pairing configurations, and egress path arrangements comply with NFPA Life Safety Code sections 18.2.3.6, 18.2.3.7, and 18.2.4.1–19.2.4.4.

View official source
Regulation text
K241
2012 NEW 
Exit access doors and exit doors are of the swinging type and are at least 
41.5 inches in clear width. In psychiatric hospitals or limited care facilities, 
doors are at least 32 inches wide. Doors not subject to patient use, in exit 
 stairway enclosures, or serving newborn nurseries shall be no less than 32 
 inches in clear width. If using a pair of doors, the doors shall be provided 
with a rabbet, bevel, or astragal at the meeting edge, at least one of the 
doors shall provide 32 inches in clear width, and the inactive leaf of the pair 
shall be secured with automatic flush bolts. 
18.2.3.6, 18.2.3.7 
 Number of Exits – Story and Compartment 
Not less than two exits, remote from each other, and accessible from every 
 part of every story are provided for each story. Each smoke compartment 
shall likewise be provided with two distinct egress paths to exits that do not 
 require the entry into the same adjacent smoke compartment. 
 18.2.4.1-18.2.4.4, 19.2.4.1-19.2.4.4 