Interior Nonbearing Wall Construction

Jurisdiction: CM Agency: Centers for Medicare & Medicaid Services
PSYCH_FACILITY (60%) SNF (100%)
Plain-English summary

This regulation specifies construction material requirements for interior nonbearing walls in Type I or II building construction, requiring noncombustible or limited-combustible materials. Walls requiring a minimum 2-hour fire resistance rating may use fire-retardant-treated wood enclosed within noncombustible or limited-combustible materials, except for shaft enclosures. This is a physical plant/life safety standard applicable to the facility type governed by the broader licensing chapter.

View official source
Regulation text
K163 Interior Nonbearing Wall Construction 
Interior nonbearing walls in Type I or II construction are constructed of 
noncombustible or limited-combustible materials. 
Interior nonbearing walls required to have a minimum 2 hour fire 
resistance rating are permitted to be fire-retardant-treated wood enclosed 
within noncombustible or limited-combustible materials, provided they are 
 not used as shaft enclosures. 
18.1.6.4, 18.1.6.5, 19.1.6.4, 19.1.6.5 