Regulation detail

K-Tag K162

Up to date
Ask Ariadne
SR
K-Tag K162 active

Roofing Systems Involving Combustibles

Jurisdiction: CM Agency: Centers for Medicare & Medicaid Services
SNF (100%)
Plain-English summary

This regulation specifies fire and life safety requirements for roofing systems that incorporate combustible materials in certain building construction types. Facilities must ensure roof coverings meet Class C fire ratings, that occupied building portions are separated from the roof system by a noncombustible floor assembly with at least 2½ inches of concrete or gypsum fill, and that any attic or unoccupied space is either left unoccupied or protected by an approved automatic sprinkler system. This is a CMS Life Safety Code survey tag applicable to healthcare facilities.

View official source
Regulation text
K162 Roofing Systems Involving Combustibles 
2012 EXISTING 
Buildings of Type I (442), Type I (332), Type II (222), or Type II (111) 
 having roof systems employing combustible roofing supports, decking or 
 roofing meet the following: 
1. roof covering meets Class C requirements.
2. roof is separated from occupied building portions with a
 noncombustible floor assembly using not less than 2½ inches concrete
or gypsum fill.
3. attic or other space is either unoccupied or protected throughout by an
approved automatic sprinkler system.
 19.1.6.2*, ASTM E108, ANSI/UL 790 
Name of Facility 2012 LIFE SAFETY CODE
Form CMS-2786R (07/2018) Page 5 

ID NOT MET N/A REMARKS PREFIX MET