Regulation detail

K-Tag K133

Up to date
Ask Ariadne
SR
K-Tag K133 active

Multiple Occupancies – Construction Type

Jurisdiction: CM Agency: Centers for Medicare & Medicaid Services
SNF (100%)
Plain-English summary

This regulation addresses construction type requirements for buildings with multiple occupancies, specifying that the most stringent construction type applies throughout unless a two-hour fire separation is provided, in which case construction types are determined separately for health care occupancies and other occupancy areas. It references NFPA Life Safety Code sections governing health care facility construction standards.

View official source
Regulation text
K133 Multiple Occupancies – Construction Type 
Where separated occupancies are in accordance with 18/19.1.3.2 or 
18/19.1.3.4, the most stringent construction type is provided throughout the 
building, unless a two hour separation is provided in accordance with 
8.2.1.3, in which case the construction type is determined as follows: 
 The construction type and supporting construction of the health care
occupancy is based on the story in which it is located in the building in
accordance with 18/19.1.6 and Tables 18/19.1.6.1.
 The construction type of the areas of the building enclosing the other
occupancies shall be based on the applicable occupancy chapters.
18.1.3.5, 19.1.3.5, 8.2.1.3