§483.90(c) Emergency Power.

Jurisdiction: CM Agency: Centers for Medicare & Medicaid Services
SNF (100%)
Plain-English summary

This regulation requires nursing facilities to maintain an emergency electrical power system that provides lighting for all entrances and exits, supports fire detection and alarm systems, and powers life support systems during normal power interruptions. When residents rely on life support equipment, an on-premises emergency generator meeting NFPA 99 standards is mandatory. Surveyors must verify periodic testing records, proper lighting coverage, and that generators transfer power within 10 seconds of outage. A Type I Essential Electrical System is required where residents use life support equipment such as ventilators.

View official source
Regulation text
F906
(Rev. 173, Issued: 11-22-17, Effective: 11-28-17, Implementation: 11-28-17) 
 
§483.90(c) Emergency Power. 
 
§483.90(c)(1) An emergency electrical power system must supply power adequate at 
least for lighting all entrances and exits; equipment to maintain the fire detection, 
alarm, and extinguishing systems; and life support systems in the event the normal 
electrical supply is interrupted. 
 
§483.90(c)(2) When life support systems are used, the facility must provide 
emergency electrical power with an emergency generator (as defined in NFPA 99, 
Health Care Facilities) that is located on the premises. 
 
Guidance: §483.90(c)(1) and (c)(2) 

“Emergency electrical power system” includes, at a minimum, a generator or 
battery-operated power system for the lighting for all entrances and exits, fire detection 
and alarm systems, and extinguishing systems. Life support systems are required to be 
powered by an emergency generator that is located on the premises, see 483.90(c)(2). 
 
An “exit” is defined as a means of egress which is lighted and has three components: an 
exit access (corridor leading to the exit), an exit (a door), and an exit discharge (door to 
the street or public way). We define an entrance as any door through which people enter 
the facility. Furthermore, when an entrance also serves as an exit, its components (exit 
access, exit, and exit discharge) must be lighted. A waiver of lighting required for both 
exits and entrances is not permitted. 
 
“Life support systems” is defined as one or more items of electrically powered 
equipment whose operation is necessary to maintain a patient or resident’s life. For 
example, ventilators, suction machines if necessary to maintain an open airway, etc.. The 
determination of whether a piece of equipment is life support is a medical determination 
dependent upon the condition of the individual residents of the facility e.g. suction 
machine maybe required “life support equipment” in a facility, depending on the needs of 
its residents. 
 
“Essential Electrical System” is defined as a system of alternate sources of power and 
all commercial distribution systems and ancillary equipment, designed to ensure 
continuity of electrical power to designated areas and functions of a health care facility 
during disruption of normal power sources, and also to minimize disruption within the 
internal wiring system. 
 
Procedures: §483.90(c)(1) and (c)(2) 
Review results of inspections by the designated State fire safety authority that the 
emergency power system has been tested periodically and is functioning in accordance 
with the Life Safety Code, NFPA 99 and NFPA 110. 
 
Check placement of lighting system to ensure proper coverage of the listed 
areas. Review records of monthly and annual tests to ensure that emergency lighting 
system for, at least, lighting all entrances and exits is operational. 
 
If life support systems are used determine if there is a working emergency generator at 
the facility. A generator is not required if a facility does not use life support systems. 
Check that the emergency generator starts and transfers power under load conditions 
within 10 seconds after interruption of normal power. Where residents are on life support 
equipment, do not test transfer switches by shutting off the power unless there is an 
uninterruptible power supply available. 
 
A type I Essential Electrical System is required to be installed if the facility uses life 
support systems and residents are on life support equipment such as a ventilator to assist 
in breathing. 
Probes: §483.90(c)(1) and (c)(2) 

Is emergency electrical service adequate? 
 
Additional guidance is available in the National Fire Protection Association’s Life Safety 
Code NFPA 101 and NFPA 99, Health Care Facilities Code, sections 18.5.1.2, 18.5.1.3 
and 18.2.9.2 and 18.2.20.5 which are surveyed in Tags K292 and K915 of the Life Safety 
code survey. 
 
Is there a working generator if the facility is using life support systems and is it 
maintained in accordance with the manufacturer’s recommendations and NFPA 99 and 
NFPA 110? 
 
Does the facility have a type I electrical system installed throughout the facility or at least 
to building areas where required in accordance with NFPA 72 and NFPA 99? 
 
If applicable, is the generator and emergency electrical system tested and maintained in 
accordance with NFPA 99 and NFPA 110 and are records of such maintained?